Electricity (Hazards from Trees) Regulations 2003

  • This version was replaced on 28 August 2017 to make a correction to regulation 4(2) under section 25(1)(j)(ii) of the Legislation Act 2012.

Schedule Growth limit zones

r 4(1)

Table 1

Distances for spans less than and equal to 150 metres in length

Voltage of conductors other than aerial bundled conductors or conductors insulated by other meansDistance in any direction from any point on conductor
(metres)
66 kV or greater4
50 kV to 66 kV3
33 kV2.5
11 kVl.6
400/230 v0.5
Voltage of aerial bundled conductors or conductors insulated by other meansDistance in any direction from any point on conductor
(metres)
Any voltage where the conductor is an aerial bundled conductor or is otherwise insulated0.5
Key:
kV = kilovolts
v = volts

Table 2

Distances for spans more than 150 metres in length

Length of span
(metres)
Vertical distance from a horizontal plane drawn from any point on conductor
(metres)
Horizontal distance from a vertical plane drawn from any point on conductor
(metres)
150 to 3004D1 = 4
D2 = 8
301 to 5004D1 = 7.5
D2 = 15
501 to 7004D1 = 15
D2 = 30
Greater than or equal to 7014D1 = 25
D2 = 50
Key:
D1 = distance for the 15% of each span at either end of the span
D2 = distance for the centre 70% of each span