Electricity (Safety) Regulations 2010

60 Certain installations must comply with Part 2 of AS/NZS 3000

(1)

The following installations or part installations must be installed, tested, inspected, and connected so as to comply with Part 2 of AS/NZS 3000 and also with the standard indicated:

(a)

an installation or part installation intended for use with electrical medical devices: AS/NZS 3003:

(b)

an installation or part installation in a hazardous area: AS/NZS 60079.14:

(c)

a connectable installation or part of a connectable installation in a mobile medical facility: NZS 6115:

(d)

a connectable installation or part of a connectable installation in a pleasure vessel: AS/NZS 3004.2:

(e)

all other connectable installations or parts of connectable installations: AS/NZS 3001:

(f)

a site installation or part of a site installation that—

(i)

is in a marina: AS/NZS 3004.1; or

(ii)

is in a show or carnival: AS/NZS 3002; or

(iii)

is intended to supply connectable installations in mobile medical facilities: NZS 6115; or

(iv)

is intended to supply any other connectable installation: AS/NZS 3001.

(2)

If any of the following are installed so as to comply with Part 2 of AS/NZS 3000, they must also comply with the standards indicated:

(a)

a refrigeration system (but not a refrigeration appliance): AS/NZS 1677.2:

(b)

an animal stunning or meat conditioning system: NZS 6116:

(c)

a stand-alone power system: AS/NZS 4509.1:

(d)

a photovoltaic array: AS/NZS 5033:

(e)

an emergency power supply in a hospital: AS/NZS 3009:

(f)

a low voltage mains parallel generation system that is connected to the national grid: AS/NZS 3010 and AS 4777.1.

Regulation 60: replaced, on 1 July 2013, by regulation 11 of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).