(1)
The following installations or part installations must be installed, tested, inspected, and connected so as to comply with Part 2 of AS/NZS 3000 and also with the standard indicated:
an installation or part installation intended for use with electrical medical devices: AS/NZS 3003:
an installation or part installation in a hazardous area: AS/NZS 60079.14:
a connectable installation or part of a connectable installation in a mobile medical facility: NZS 6115:
a connectable installation or part of a connectable installation in a pleasure vessel: AS/NZS 3004.2:
all other connectable installations or parts of connectable installations: AS/NZS 3001:
a site installation or part of a site installation that—
is in a marina: AS/NZS 3004.1; or
is in a show or carnival: AS/NZS 3002; or
is intended to supply connectable installations in mobile medical facilities: NZS 6115; or
is intended to supply any other connectable installation: AS/NZS 3001.
(2)
If any of the following are installed so as to comply with Part 2 of AS/NZS 3000, they must also comply with the standards indicated:
a refrigeration system (but not a refrigeration appliance): AS/NZS 1677.2:
an animal stunning or meat conditioning system: NZS 6116:
a stand-alone power system: AS/NZS 4509.1:
a photovoltaic array: AS/NZS 5033:
an emergency power supply in a hospital: AS/NZS 3009:
a low voltage mains parallel generation system that is connected to the national grid: AS/NZS 3010 and AS 4777.1.