Building Regulations 1992
Building Regulations 1992
Checking for alerts... Loading...
Building Regulations 1992
Reprint as at 1 February 2009

Building Regulations 1992
(SR 1992/150)
Building Regulations 1992: revoked (with regulation 3 and Schedule 1 continued in force), on 31 March 2005, by regulation 8(1) of the Building (Forms) Regulations 2004 (SR 2004/385).
Catherine A Tizard, Governor-General
Order in Council
At Wellington this 8th day of June 1992
Present:
Her Excellency the Governor-General in Council
Note
Changes authorised by section 17C of the Acts and Regulations Publication Act 1989 have been made in this reprint.
A general outline of these changes is set out in the notes at the end of this reprint, together with other explanatory material about this reprint.
These regulations are administered by the Department of Building and Housing.
Pursuant to the Building Act 1991, Her Excellency the Governor-General, acting by and with the advice and consent of the Executive Council, hereby makes the following regulations.
Contents
| 1 | Title and commencement [Revoked] | ||
| 2 | Interpretation [Revoked] | ||
| 3 | Building code | ||
| 4 | Forms [Revoked] | ||
| 5 | Project information memorandum [Revoked] | ||
| 6 | Building consent [Revoked] | ||
| 7 | Notice that building work is ready for inspection [Revoked] | ||
| 8 | Inspection reports by building certifiers [Revoked] | ||
| 9 | Charges by Building Industry Authority [Revoked] | ||
| 10 | Territorial authority records [Revoked] | ||
| 11 | Transitional provisions and savings [Revoked] | ||
| Gazette Information | |||
| Reprint notes | |||
1 Title and commencement
[Revoked]Regulation 1: revoked, on 31 March 2005, by regulation 8(1) of the Building (Forms) Regulations 2004 (SR 2004/385).
2 Interpretation
[Revoked]Regulation 2: revoked, on 31 March 2005, by regulation 8(1) of the Building (Forms) Regulations 2004 (SR 2004/385).
3 Building code
(1)
In accordance with Part 6 of the Act, the building code shall be the building code set out in Schedule 1.
(2)
Except as otherwise provided by the Act, each building shall achieve the performance criteria specified in the building code for the classified use of that building, and, if the building has more than 1 classified use, any part of it used for more than 1 classified use shall achieve the performance criteria for each such classified use.
(3)
The classified use or uses of a building or part of a building shall be the ones that most closely correspond to the intended use or uses of that building or part of that building.
Regulation 3: continued in force, on 31 March 2005, by regulation 8(2)(a) of the Building (Forms) Regulations 2004 (SR 2004/385).
4 Forms
[Revoked]Regulation 4: revoked for all purposes, on 31 May 2006, by regulation 8(2)(b) of the Building (Forms) Regulations 2004 (SR 2004/385).
5 Project information memorandum
[Revoked]Regulation 5: revoked, on 31 March 2005, by regulation 8(1) of the Building (Forms) Regulations 2004 (SR 2004/385).
6 Building consent
[Revoked]Regulation 6: revoked, on 31 March 2005, by regulation 8(1) of the Building (Forms) Regulations 2004 (SR 2004/385).
7 Notice that building work is ready for inspection
[Revoked]Regulation 7: revoked, on 31 March 2005, by regulation 8(1) of the Building (Forms) Regulations 2004 (SR 2004/385).
8 Inspection reports by building certifiers
[Revoked]Regulation 8: revoked, on 31 March 2005, by regulation 8(1) of the Building (Forms) Regulations 2004 (SR 2004/385).
9 Charges by Building Industry Authority
[Revoked]Regulation 9: revoked, on 31 March 2005, by regulation 8(1) of the Building (Forms) Regulations 2004 (SR 2004/385).
10 Territorial authority records
[Revoked]Regulation 10: revoked, on 31 March 2005, by regulation 8(1) of the Building (Forms) Regulations 2004 (SR 2004/385).
11 Transitional provisions and savings
[Revoked]Regulation 11: revoked, on 31 March 2005, by regulation 8(1) of the Building (Forms) Regulations 2004 (SR 2004/385).
Schedule 1 The building code
| Table of Contents | |
| General provisions | |
| A1 | Classified uses |
| A2 | Interpretation |
| Stability | |
| B1 | Structure |
| B2 | Durability |
| Fire safety | |
| C1 | Outbreak of fire |
| C2 | Means of escape |
| C3 | Spread of fire |
| C4 | Structural stability during fire |
| Access | |
| D1 | Access routes |
| D2 | Mechanical installations for access |
| Moisture | |
| E1 | Surface water |
| E2 | External moisture |
| E3 | Internal moisture |
| Safety of users | |
| F1 | Hazardous agents on site |
| F2 | Hazardous building materials |
| F3 | Hazardous substances and processes |
| F4 | Safety from falling |
| F5 | Construction and demolition hazards |
| F6 | Visibility in escape routes |
| F7 | Warning systems |
| F8 | Signs |
| Services and facilities | |
| G1 | Personal hygiene |
| G2 | Laundering |
| G3 | Food preparation and prevention of contamination |
| G4 | Ventilation |
| G5 | Interior environment |
| G6 | Airborne and impact sound |
| G7 | Natural light |
| G8 | Artificial light |
| G9 | Electricity |
| G10 | Piped services |
| G11 | Gas as an energy source |
| G12 | Water supplies |
| G13 | Foul water |
| G14 | Industrial liquid waste |
| G15 | Solid waste |
| Energy efficiency | |
| H1 | Energy efficiency |
Clause A1—Classified Uses
1.0 Explanation
1.0.1
For the purposes of this building code buildings are classified according to type, under seven categories.
1.0.2
A building with a given classified use may have one or more intended uses as defined in the Act.
2.0 Housing
2.0.1
Applies to buildings or use where there is self care and service (internal management). There are three types:
2.0.2
Detached dwellings
Applies to a building or use where a group of people live as a single household or family. Examples: a holiday cottage, boarding house accommodating fewer than 6 people, dwelling or hut.
2.0.3
Multi-unit dwelling
Applies to a building or use which contains more than one separate household or family. Examples: an attached dwelling, flat or multi-unit apartment.
2.0.4
Group dwelling
Applies to a building or use where groups of people live as one large extended family. Examples: within a commune or marae.
3.0 Communal residential
3.0.1
Applies to buildings or use where assistance or care is extended to the principal users. There are two types:
3.0.2
Community service
Applies to a residential building or use where limited assistance or care is extended to the principal users. Examples: a boarding house, hall of residence, holiday cabin, backcountry hut, hostel, hotel, motel, nurse’s home, retirement village, time-share accommodation, a work camp, or camping ground.
3.0.3
Community care
Applies to a residential building or use where a large degree of assistance or care is extended to the principal users. There are two types:
(a)
Unrestrained; where the principal users are free to come and go. Examples: a hospital, an old people’s home or a health camp.
(b)
Restrained; where the principal users are legally or physically constrained in their movements. Examples: a borstal or drug rehabilitation centre, an old people’s home where substantial care is extended, a prison or hospital.
Schedule 1 clause A1 3.0.2: amended, on 31 October 2008, by regulation 4 of the Building (Building Code: Backcountry Huts) Amendment Regulations 2008 (SR 2008/358).
4.0 Communal non-residential
4.0.1
Applies to a building or use being a meeting place for people where care and service is provided by people other than the principal users. There are two types:
4.0.2
Assembly service
Applies to a building or use where limited care and service is provided. Examples: a church, cinema, clubroom, hall, museum, public swimming pool, stadium, theatre, or whare runanga (the assembly house).
4.0.3
Assembly care
Applies to a building or use where a large degree of care and service is provided. Examples: an early childhood education and care centre, college, day care institution, centre for handicapped persons, kindergarten, school or university.
Schedule 1 clause A1 4.0.3: amended, on 1 December 2008, by section 60(2) of the Education Amendment Act 2006 (2006 No 19).
5.0 Commercial
5.0.1
Applies to a building or use in which any natural resources, goods, services or money are either developed, sold, exchanged or stored. Examples: an amusement park, auction room, bank, car-park, catering facility, coffee bar, computer centre, fire station, funeral parlour, hairdresser, library, office (commercial or government), Police station, post office, public laundry, radio station, restaurant, service station, shop, showroom, storage facility, television station or transport terminal.
6.0 Industrial
6.0.1
Applies to a building or use where people use material and physical effort to:
(a)
extract or convert natural resources,
(b)
produce goods or energy from natural or converted resources,
(c)
repair goods, or
(d)
store goods (ensuing from the industrial process).
Examples: an agricultural building, agricultural processing facility, aircraft hanger, factory, power station, sewage treatment works, warehouse or utility.
7.0 Outbuildings
7.0.1
Applies to a building or use which may be included within each classified use but are not intended for human habitation, and are accessory to the principal use of associated buildings. Examples: a carport, farm building, garage, greenhouse, machinery room, private swimming pool, public toilet, or shed.
8.0 Ancillary
8.0.1
Applies to a building or use not for human habitation and which may be exempted from some amenity provisions, but which are required to comply with structural and safety-related aspects of the building code. Examples: a bridge, derrick, fence, free-standing outdoor fireplace, jetty, mast, path, platform, pylon, retaining wall, tank, tunnel or dam.
Clause A2—Interpretation
In this building code unless the context otherwise requires, words shall have the meanings given under this clause. Meanings given in the Building Act 1991 apply equally to the building code.
access route a continuous route that permits people and goods to move between the apron or construction edge of the building to spaces within a building, and between spaces within a building
accessible having features to permit use by people with disabilities
accessible route an access route usable by people with disabilities. It shall be a continuous route that can be negotiated unaided by a wheelchair user. The route shall extend from street boundary or carparking area to those spaces within the building required to be accessible to enable people with disabilities to carry out normal activities and processes within the building
adequate means adequate to achieve the objectives of the building code
adjacent building a nearby building, including an adjoining building, whether or not erected on other property
allotment has the meaning ascribed to it by section 4 of the Act as follows: meaning of allotment—
(1)
In this Act, the term “allotment” means any parcel of land that is a continuous area of land and whose boundaries are shown on a survey plan that is:
(a)
subject to the Land Transfer Act 1952 and is comprised in one certificate of title or for which one certificate of title could be issued under that Act; or
(b)
not subject to that Act and was acquired by its owner under one instrument of conveyance.
(2)
For the purpose of subsection (1), the subdivision shown on the survey plan referred to in that subsection is:
(a)
the subdivision approved by way of a subdivision consent granted under the Resource Management Act 1991; or
(b)
the subdivision allowed or granted under any other Act.
(3)
For the purposes of subsection (1), and allotment shall be deemed to be a continuous area of land notwithstanding that part of it is physically separated from any other part by a road or in any other manner whatsoever, unless the division of the allotment into such parts has been allowed by a subdivision consent granted under the Resource Management Act 1991 or a subdivision approval under any former enactment relating to the subdivision of land
alter, in relation to a building, includes to rebuild, re-erect, repair, enlarge and extend; and alteration has a corresponding meaning
amenity means an attribute of a building which contributes to the health, physical independence, and well being of the building’s users but which is not associated with disease or a specific illness
approved temperature data means the temperature data contained in A I Tomlinson and J Sansom, Temperature Normals for New Zealand for the period 1961 to 1990 (NIWA, ISBN 0478083343)
backcountry hut means a building that—
(a)
is located on land that is administered by the Department of Conservation for conservation, recreational, scientific, or other related purposes, including any land administered under any of the following:
(i)
(ii)
(iii)
the Reserves Act 1977; and
(b)
is intended to provide overnight shelter to any person who may visit and who carries his or her own food, bedding, clothing, and outdoor equipment; and
(c)
contains only basic facilities, which may include (but are not limited to) any or all of the following:
(i)
sleeping platforms or bunks:
(ii)
mattresses:
(iii)
food preparation surfaces:
(iv)
appliances for heating:
(v)
appliances for cooking:
(vi)
toilets; and
(d)
has been certified by the Director-General as being in a location that wheelchair users are unlikely to be able to visit; and
(e)
is intended to be able to sleep—
(i)
no more than 20 people in its backcountry hut sleeping area; and
(ii)
no more than 40 people in total; and
(f)
does not contain any connection, except by radiocommunications, to a network utility operator
backcountry hut sleeping area means the area of a backcountry hut that contains sleeping platforms, bunks, or beds that are—
(a)
within the same room as a food preparation or eating area; or
(b)
in a fully enclosed room that is separate from any food preparation or eating area and has—
(i)
internal walls that limit the spread of fire; and
(ii)
the means of direct egress to outside the hut
building has the meaning ascribed to it by section 3 of the Act as follows: meaning of building—
(1)
In this Act, unless the context otherwise requires, the term “building” means any temporary or permanent movable or immovable structure (including any structure intended for occupation by people, animals, machinery, or chattels); and includes any mechanical, electrical, or other systems, and any utility systems, attached to and forming part of the structure whose proper operation is necessary for compliance with the building code; but does not include:
(a)
systems owned or operated by a network utility operator for the purpose of reticulation of other property; or
(b)
cranes, including any cranes as defined in any regulations in force under the Health and Safety in Employment Act 1992; or
(c)
cablecars, cableways, ski tows, and other similar stand alone machinery systems, whether or not incorporated within any other structure; or
(d)
any description of vessel, boat, ferry, or craft used in navigation, whether or not it has any means of propulsion, and regardless of that means; nor does it include—
(i)
a barge, lighter, or other like vessel:
(ii)
a hovercraft or other thing deriving full or partial support in the atmosphere from the reactions of air against the surface of the water over which it operates:
(iii)
a submarine or other thing used in navigation while totally submerged; or
(e)
vehicles and motor vehicles (including vehicles and motor vehicles as defined in section 2(1) of the Transport Act 1962 and section 2(1) of the Transport (Vehicle and Driver Registration and Licensing) Act 1986), but not including vehicles and motor vehicles, whether movable or immovable, which are used exclusively for permanent or long-term residential purposes; or
(ea)
aircraft, including any machine that can derive support in the atmosphere from the reactions of the air otherwise than by the reactions of the air against the surface of the earth; or
(f)
containers as defined in section 2(1) of the Hazardous Substances and New Organisms Act 1996; or
(g)
magazines as defined in section 2 of the Explosives Act 1957; or
(h)
scaffolding used in the course of the construction process; or
(i)
falsework used in the course of the construction process.
(2)
For the purposes of Part 9 of this Act, a building consent, a code compliance certificate, and a compliance schedule the term building also includes—
(a)
any part of a building; and
(b)
any 2 or more buildings which, on completion of any building work, are intended to be managed as 1 building with a common use and a common set of ownership arrangements.
(3)
For the purposes of subclause (2) of this definition, where any utility system or any part of any utility system—
(a)
is external to the building; and
(b)
is also connected to or is intended to be connected to—
(i)
a network under the control of a network utility operator; or
(ii)
some other facility which is able to provide for the successful functioning of the utility system in accordance with its intended design—
that utility system or that part of the utility system shall be deemed to be part of a building.
(4)
Notwithstanding the provisions of subclause (3) of this definition, where a septic tank is connected to a building utility system the septic tank shall be deemed to form part of that building utility system
building certifier means a person approved as a building certifier by the Authority under Part 7 of the Act
building code means the building code made under Part 6 of the Act
building consent means a consent to carry out building work granted by a territorial authority under Part 5 of the Act; and includes all conditions to which the consent is subject
building element any structural or non-structural component and assembly incorporated into or associated with a building. Included are fixtures, services, drains, permanent mechanical installations for access, glazing, partitions, ceilings and temporary supports
building height the vertical distance between the floor level of the lowest final exit from the building; and the highest floor level containing or supporting any purpose group other than IE, IA or ID, or penthouses used to enclose stairways, liftshafts or machinery rooms located on or within the roof
building performance index (BPI), in relation to a building, means the heating energy of the building divided by the product of the heating degrees total and the sum of the floor area and the total wall area, and so is calculated in accordance with the following formula:
| BPI = | heating energy | ||
| heating degrees total × (floor area + total wall area) |
building work work for or in connection with the construction, alteration, demolition, or removal of a building; and includes sitework
code compliance certificate means a certificate to that effect issued by a territorial authority or a building certifier pursuant to section 43 of the Act
combustion appliance a slow combustion stove, a free standing metal cone fireplace, a cast iron pot belly stove, an oil burning space heater, or a vented gas burning heater
compliance schedule means a compliance schedule issued under section 44 of the Act
concealed space any part of the space within a building that cannot be seen from an occupied space
construct in relation to a building, includes to build, erect, prefabricate, and relocate; and construction has a corresponding meaning
contaminant has the meaning ascribed to it by the Resource Management Act 1991
Department of Conservation means the department of State established by section 5 of the Conservation Act 1987
Director-General has the same meaning as in section 2(1) of the Conservation Act 1987
drain a pipe normally laid below ground level including fittings and equipment and intended to convey foul water or surface water to an outfall
electrical fixed appliance an electrical appliance which is fixed-wired to the electrical installation, or intended to remain permanently attached and form part of the building
electrical installation any electrical fixed appliances, and components used in the reticulation of electricity, which are intended to remain permanently attached to and form part of the building
electrical supply system the source of electricity external to the electrical installation
escape route a continuous unobstructed route from any occupied space in a building to a final exit to enable occupants to reach a safe place, and shall comprise one or more of the following: open paths, protected paths and safe paths
essential service in the context of an electrical installation means emergency lighting, firemen’s lifts, alarms, water pumps, sprinklers, detectors, ventilation systems and public address systems necessary for the safety of people in buildings
estimated value the value of building work shall be the aggregate of the values, determined in accordance with section 10 of the Goods and Services Tax Act 1985, of all goods and services to be supplied for that building work
evacuation time the time taken by the occupants of the building to evacuate the building to a final exit
exitway all parts of an escape route protected by fire or smoke separations, or by distance when exposed to open air, and terminating at a final exit
external wall any exterior face of a building within 30° of vertical, consisting of primary and/or secondary elements intended to provide protection against the outdoor environment, but which may also contain unprotected areas
final exit the point at which an escape route terminates by giving direct access to a safe place
fire the state of combustion during which flammable materials burn producing heat, toxic gases, or smoke or flame or any combination of these
firecell any space including a group of contiguous spaces on the same or different levels within a building, which is enclosed by any combination of fire separations, external walls, roofs, and floors
fire hazard means the danger in terms of potential harm and degree of exposure arising from the start and spread of fire and the smoke and gases that are thereby generated
fire intensity the rate release of calorific energy in watts, determined either theoretically or empirically, as applicable
fire load the sum of the net calorific values of the combustible contents which can reasonably be expected to burn within a firecell, including furnishings, built-in and removable materials, and building elements. The calorific values shall be determined at the ambient moisture content or humidity. (The unit of measurement is MJ)
fire resisting closure a fire rated device or assembly for closing an opening through a fire separation. It shall have a FRR of no less than that required for the fire separation
fire resistance rating (FRR) the term used to classify fire resistance of primary and secondary elements as determined in the standard test for fire resistance, or in accordance with a specific calculation method verified by experimental data from standard fire resistance tests. It comprises three numbers giving the time in minutes for which each of the criteria stability, integrity and insulation are satisfied, and is presented always in that order
fire safety system the combination of all methods used in a building to warn people of an emergency, provide for safe evacuation, and restrict the spread of fire, and includes both active and passive protection
fire separation any building element which separates firecells or firecells and safe paths, and provides a specific fire resistance rating
fixture an article intended to remain permanently attached to and form part of a building
floor area, in relation to a building, means the floor area (expressed in square metres) of all interior spaces used for activities normally associated with domestic living
foul water the discharge from any sanitary fixtures or sanitary appliances
foul water drainage system drains joints and fittings normally laid underground and used specifically for the conveyance of water from the plumbing system to an outfall
habitable space a space used for activities normally associated with domestic living, but excludes any bathroom, laundry, water-closet, pantry, walk-in wardrobe, corridor, hallway, lobby, clothes-drying room, or other space of a specialised nature occupied neither frequently nor for extended periods
handrail a rail to provide both support to, or assist with the movement of a person
hazardous creating an unreasonable risk to people of bodily injury or deterioration of health
hazardous substance has the meaning ascribed to it by the Fire Service Act 1975
heating degrees, in relation to a location and a heating month, means the degrees obtained by subtracting from a base temperature of 14°C the mean (calculated using the approved temperature data) of the outdoor temperatures at that location during that month
heating degrees total, in relation to a location and a year, means whichever is the greater of the following:
(a)
the value of 12; and
(b)
the sum of all the heating degrees (calculated using the approved temperature data) for all of the heating months of the year
heating energy, in relation to a building, means the energy from a network utility operator or a depletable resource (expressed in kilowatt-hours, and calculated using the Building Research Association of New Zealand’s ALF 3, The ‘Annual Loss Factor Method’, A design tool for energy efficient houses (3rd edition, April 2000) or some other method that can be correlated with that manual) needed to maintain the building at all times within a year at a constant internal temperature under the following standard conditions:
(a)
a continuous temperature of 20°C throughout the building:
(b)
an air change rate of 1 change per hour or the actual air leakage rate, whichever is the greater:
(c)
a heat emission contribution arising from internal heat sources for any period in the year of 1 000 kilowatt-hours for the first 50 m2 of floor area, and 10 kilowatt-hours for every additional square metre of floor area:
(d)
no allowance for—
(i)
carpets; or
(ii)
blinds, curtains, or drapes, on windows:
(e)
windows to have a shading coefficient of 0.6 (made up of 0.8 for windows and recesses and 0.75 for site shading)
heating month, in relation to a location, means a month in which a base temperature of 14°C is greater than the mean (calculated using the approved temperature data) of the outdoor temperatures at that location during that month
household unit means any building or group of buildings, or part of any building or group of buildings, used or intended to be used solely or principally for residential purposes and occupied or intended to be occupied exclusively as the home or residence of not more than one household; but does not include a hostel or boardinghouse or other specialised accommodation
HVAC system, for the purposes of performance H1.3.6 and in relation to a building, means a mechanical, electrical, or other system for modifying air temperature, modifying air humidity, providing ventilation, or doing all or any of those things, in a space within the building
illuminance the luminous flux falling onto a unit area of surface
impact insulation class (IIC) a single number rating derived from measured values of normalised sound pressure impact levels in accordance with Method ASTM E492, Annex A1. Laboratory Measurement of Impact Sound Transmission Through Floor-Ceiling Assemblies Using the Tapping Machine. It provides an estimate of the impact sound insulating performance of a floor-ceiling assembly
impervious that which does not allow the passage of moisture
insulation in the context of fire protection, the time in minutes for which a prototype specimen of a fire separation, when subjected to the standard test for fire resistance, has limited the transmission of heat through the specimen
integrity in the context of fire protection, the time in minutes for which a prototype specimen of a fire separation, when subjected to the standard test for fire resistance, has prevented the passage of flame or hot gases
intended use of a building includes—
(a)
any reasonably foreseeable occasional other use that is not incompatible with the intended use; and
(b)
normal maintenance; and
(c)
activities taken in response to fire or any other reasonably foreseeable emergency—but does not include any other maintenance and repairs or rebuilding
network utility operator means a person who—
(a)
undertakes the distribution or transmission by pipeline of natural or manufactured gas, petroleum, or geothermal energy; or
(b)
is an electricity operator or an electricity distributor as defined by section 2(1) of the Electricity Act 1992 for the purposes of any works as defined by that Act; or
(c)
undertakes the piped distribution of potable water for supply; or
(d)
is the operator of a sewerage system or a stormwater drainage system
occupied space any space within a building in which a person will be present from time to time during the intended use of the building
open path that part of an escape route (including dead ends) not protected by fire or smoke separations, and which terminates at a final exit or exitway
other property means any land or buildings or part thereof which are—
(a)
not held under the same allotment; or
(b)
not held under the same ownership—
and includes any road
outdoor air air as typically comprising by volume. (i) oxygen 20.94% (ii) carbon dioxide 0.03% (iii) nitrogen and other inert gases 79.03%
outfall that part of the disposal system receiving surface water or foul water from the drainage system. For foul water the outfall may include a sewer or a septic tank. For surface water, the outfall may include a natural water course, kerb and channel, or soakage system
people with disabilities people whose ability to use buildings is affected by mental, physical, hearing or sight impairment
plumbing system pipes, joints and fittings laid above ground and used for the conveyance of foul water to the foul water drain, and includes vent pipes
protected path that portion of an exitway within a firecell which is protected from the effects of smoke by smoke separations
principal user a member of the primary group for which a building was constructed, and therefore explicitly excludes persons or groups of persons providing care or control of that principal user group
purpose group the classification of spaces within a building according to the activity for which the spaces are used
radiocommunications has the same meaning as in section 2(1) of the Radiocommunications Act 1989
reasonably visible, in relation to a specified feature, and for the purposes of Clause F6, means that the specified feature is visible to a person who—
(a)
is 10 metres from it, or the greatest distance from it that it is possible to go in the open space surrounding it, whichever is the lesser; and
(b)
has sight that is not defective, or is corrected (for example, by an optical appliance)
risk group C, for the purposes of performance F6.3.4, means buildings not in risk group A or risk group B
safe path that part of an exitway which is protected from the effects of fire by fire separations, external walls or by distance when exposed to open air
safe place a place of safety in the vicinity of a building, from which people may safely disperse after escaping the effects of a fire. It may be a place such as a street, open space, public space or an adjacent building
sanitary appliance an appliance which is intended to be used for sanitation, but which is not a sanitary fixture. Included are machines for washing dishes and clothes
sanitary fixture any fixture which is intended to be used for sanitation
sanitation the term used to describe the activities of washing and/or excretion carried out in a manner or condition such that the effect on health is minimised, with regard to dirt and infection
sewer a drain that is under the control of, or maintained by, a network utility operator
sitework means work on a building site, including earthworks, preparatory to or associated with the construction, alteration, demolition, or removal of a building
smoke separation any vertical, horizontal or inclined building element with known smoke-stopping or smoke-leakage characteristics
sound transmission class (STC) a single number rating derived from measured values of transmission loss in accordance with classification ASTM E413, Determination of Sound Transmission Class. It provides an estimate of the performance of a partition in certain common sound insulation situations
specified features, for the purposes of Clause F6, means the following:
(a)
building elements that may act as obstructions:
(b)
(c)
changes in direction:
(d)
stairs and ramps:
(e)
escape doors:
(f)
entries to a safe place
specified intended life has the meaning ascribed to it by subsection (2) of section 39 of the Act as follows: “Specified intended life”
, in relation to a building, means the period of time, as stated in an application for a building consent or in the consent itself, for which the building is proposed to be used for its intended use
stability in the context of fire protection, the time in minutes for which a prototype specimen of a primary element, when subjected to the standard test for fire resistance, has continued to carry its fire design load without failure
standard year for the purposes of determining natural lighting, the hours between 8 am and 5 pm each day with an allowance being made for daylight saving
surface water all naturally occurring water, other than sub-surface water, which results from rainfall on the site or water flowing onto the site, including that flowing from a drain, stream, river, lake or sea
territorial authority has the meaning ascribed to it by section 2 of the Local Government Act 1974; and includes any organisation which is authorised to permit structures pursuant to section 12(1)(b) of the Resource Management Act 1991
thermal resistance the resistance to heat flow of a given component of a building element. It is equal to the air temperature difference (°C) needed to produce unit heat flux (W/m2) through unit area (m2) under steady conditions. The units are °Cm2/W
total wall area, in relation to a building, means the sum (expressed in square metres) of the following:
(a)
the wall area of the building; and
(b)
the area (expressed in square metres) of all vertical glazing in external walls of the building
travel distance the length of the escape route as a whole or the individual lengths of its parts, namely: (a) open paths; (b) protected paths; and (c) safe paths
unprotected area in relation to an external wall of a building means:
(a)
any part of the external wall which has less than the required FRR. For example, a non fire rated window, door or other opening, or sheet metal:
(b)
any part of the external wall which has combustible material more than 1 mm thick attached or applied to its external face, whether for cladding or any other purpose
wall area, in relation to a building, means the area (expressed in square metres) of internally exposed external walls, including any door openings, of the building
water main a water supply pipe that is under the control of, or maintained by a network utility operator
water supply system pipes, fittings and tanks used or intended to be used for the storage and reticulation of water from a water main or other water source, to sanitary fixtures, sanitary appliances and fittings within a building.
Schedule 1 clause A2 approved temperature data: inserted, on 31 October 2007, by regulation 4(2) of the Building Amendment Regulations (No 2) 2007 (SR 2007/226).
Schedule 1 clause A2 backcountry hut: inserted, on 31 October 2008, by regulation 5 of the Building (Building Code: Backcountry Huts) Amendment Regulations 2008 (SR 2008/358).
Schedule 1 clause A2 backcountry hut sleeping area: inserted, on 31 October 2008, by regulation 5 of the Building (Building Code: Backcountry Huts) Amendment Regulations 2008 (SR 2008/358).
Schedule 1 clause A2 building (1)(b): substituted, on 22 December 1994, by regulation 3(1)(a) of the Building Regulations 1992, Amendment No 1 (SR 1994/263).
Schedule 1 clause A2 building (1)(d): substituted, on 22 December 1994, by regulation 3(1)(b) of the Building Regulations 1992, Amendment No 1 (SR 1994/263).
Schedule 1 clause A2 building (1)(ea): inserted, on 22 December 1994, by regulation 3(1)(c) of the Building Regulations 1992, Amendment No 1 (SR 1994/263).
Schedule 1 clause A2 building (1)(f): amended, on 2 July 2001, pursuant to section 150(1) of the Hazardous Substances and New Organisms Act 1996 (1996 No 30).
Schedule 1 clause A2 building (2): amended, on 22 December 1994, by regulation 3(1)(d) of the Building Regulations 1992, Amendment No 1 (SR 1994/263).
Schedule 1 clause A2 building (3): amended, on 22 December 1994, by regulation 3(1)(e) of the Building Regulations 1992, Amendment No 1 (SR 1994/263).
Schedule 1 clause A2 building (4): amended, on 22 December 1994, by regulation 3(1)(f) of the Building Regulations 1992, Amendment No 1 (SR 1994/263).
Schedule 1 clause A2 building performance index: revoked, on 31 October 2007, by regulation 4(1) of the Building Amendment Regulations (No 2) 2007 (SR 2007/226).
Schedule 1 clause A2 building performance index (BPI): inserted, on 31 October 2007, by regulation 4(1) of the Building Amendment Regulations (No 2) 2007 (SR 2007/226).
Schedule 1 clause A2 climate zone 1: revoked, on 30 September 2008, by regulation 7(2) of the Building Amendment Regulations (No 2) 2007 (SR 2007/226).
Schedule 1 clause A2 climate zone 2: revoked, on 30 September 2008, by regulation 7(2) of the Building Amendment Regulations (No 2) 2007 (SR 2007/226).
Schedule 1 clause A2 climate zone 3: revoked, on 30 September 2008, by regulation 7(2) of the Building Amendment Regulations (No 2) 2007 (SR 2007/226).
Schedule 1 clause A2 cool location: revoked, on 30 September 2008, by regulation 7(2) of the Building Amendment Regulations (No 2) 2007 (SR 2007/226).
Schedule 1 clause A2 degree-day: revoked, on 30 September 2008, by regulation 7(2) of the Building Amendment Regulations (No 2) 2007 (SR 2007/226).
Schedule 1 clause A2 degree-day total: revoked, on 30 September 2008, by regulation 7(2) of the Building Amendment Regulations (No 2) 2007 (SR 2007/226).
Schedule 1 clause A2 Department of Conservation: inserted, on 31 October 2008, by regulation 5 of the Building (Building Code: Backcountry Huts) Amendment Regulations 2008 (SR 2008/358).
Schedule 1 clause A2 Director-General: inserted, on 31 October 2008, by regulation 5 of the Building (Building Code: Backcountry Huts) Amendment Regulations 2008 (SR 2008/358).
Schedule 1 clause A2 floor area: inserted, on 31 October 2007, by regulation 4(2) of the Building Amendment Regulations (No 2) 2007 (SR 2007/226).
Schedule 1 clause A2 heating degrees: inserted, on 31 October 2007, by regulation 4(2) of the Building Amendment Regulations (No 2) 2007 (SR 2007/226).
Schedule 1 clause A2 heating degrees total: inserted, on 31 October 2007, by regulation 4(2) of the Building Amendment Regulations (No 2) 2007 (SR 2007/226).
Schedule 1 clause A2 heating energy: inserted, on 31 October 2007, by regulation 4(2) of the Building Amendment Regulations (No 2) 2007 (SR 2007/226).
Schedule 1 clause A2 heating month: inserted, on 31 October 2007, by regulation 4(2) of the Building Amendment Regulations (No 2) 2007 (SR 2007/226).
Schedule 1 clause A2 HVAC system: inserted, on 1 February 2009, by regulation 4 of the Building (Building Code: Energy Efficiency of Temperature, Humidity, and Ventilation Systems) Amendment Regulations 2008 (SR 2008/97).
Schedule 1 clause A2 network utility operator paragraph (b): substituted, on 29 December 2000, by regulation 3(3) of the Building Amendment Regulations 2000 (SR 2000/119).
Schedule 1 clause A2 old measure building performance index: revoked, on 30 September 2008, by regulation 7(2) of the Building Amendment Regulations (No 2) 2007 (SR 2007/226).
Schedule 1 clause A2 radiocommunications: inserted, on 31 October 2008, by regulation 5 of the Building (Building Code: Backcountry Huts) Amendment Regulations 2008 (SR 2008/358).
Schedule 1 clause A2 reasonably visible: inserted, on 21 June 2007, by regulation 6(2) of the Building Amendment Regulations 2007 (SR 2007/124).
Schedule 1 clause A2 risk group A: inserted, on 21 June 2007, by regulation 6(2) of the Building Amendment Regulations 2007 (SR 2007/124).
Schedule 1 clause A2 risk group B: inserted, on 21 June 2007, by regulation 6(2) of the Building Amendment Regulations 2007 (SR 2007/124).
Schedule 1 clause A2 risk group C: inserted, on 21 June 2007, by regulation 6(2) of the Building Amendment Regulations 2007 (SR 2007/124).
Schedule 1 clause A2 specified features: inserted, on 21 June 2007, by regulation 6(2) of the Building Amendment Regulations 2007 (SR 2007/124).
Schedule 1 clause A2 thermal resistance: amended, on 29 December 2000, by regulation 3(4) of the Building Amendment Regulations 2000 (SR 2000/119).
Schedule 1 clause A2 total wall area: inserted, on 31 October 2007, by regulation 4(2) of the Building Amendment Regulations (No 2) 2007 (SR 2007/226).
Schedule 1 clause A2 wall area: inserted, on 31 October 2007, by regulation 4(2) of the Building Amendment Regulations (No 2) 2007 (SR 2007/226).
Schedule 1 clause A2 warm location: revoked, on 30 September 2008, by regulation 7(2) of the Building Amendment Regulations (No 2) 2007 (SR 2007/226).
Schedule 1 clause A2 water supply system: amended, on 22 December 1994, by regulation 3(2)(e) of the Building Regulations 1992, Amendment No 1 (SR 1994/263).
Schedule 1 clause A2 water supply system: amended, on 22 December 1994, by regulation 3(2)(f) of the Building Regulations 1992, Amendment No 1 (SR 1994/263).
Clause B1—Structure
| Provisions | Limits on application |
|---|---|
Objective |
|
B1.1The objective of this provision is to: (a)safeguard people from injury caused by structural failure, (b)safeguard people from loss of amenity caused by structural behaviour, and (c)protect other property from physical damage caused by structural failure. |
|
Functional requirement |
|
B1.2Buildings, building elements and sitework shall withstand the combination of loads that they are likely to experience during construction or alteration and throughout their lives. |
|
Performance |
|
B1.3.1Buildings, building elements and sitework shall have a low probability of rupturing, becoming unstable, losing equilibrium, or collapsing during construction or alteration and throughout their lives. |
|
B1.3.2Buildings, building elements and sitework shall have a low probability of causing loss of amenity through undue deformation, vibratory response, degradation, or other physical characteristics throughout their lives, or during construction or alteration when the building is in use. |
|
B1.3.3Account shall be taken of all physical conditions likely to affect the stability of buildings, building elements and sitework, including: (a)self-weight, (b)imposed gravity loads arising from use, (c)temperature, (d)earth pressure, (e)water and other liquids, (f)earthquake, (g)snow, (h)wind, (i)fire, (j)impact, (k)explosion, (l)reversing or fluctuating effects, (m)differential movement, (n)vegetation, (o)adverse effects due to insufficient separation from other buildings, (p)influence of equipment, services, non-structural elements and contents, (q)time dependent effects including creep and shrinkage, and (r)removal of support. |
|
B1.3.4Due allowance shall be made for: (a)the consequences of failure, (b)the intended use of the building, (c)effects of uncertainties resulting from construction activities, or the sequence in which construction activities occur, (d)variation in the properties of materials and the characteristics of the site, and (e)accuracy limitations inherent in the methods used to predict the stability of buildings. |
|
B1.3.5The demolition of buildings shall be carried out in a way that avoids the likelihood of premature collapse. |
|
B1.3.6Sitework, where necessary, shall be carried out to: (a)provide stability for construction on the site, and (b)avoid the likelihood of damage to other property. |
|
B1.3.7Any sitework and associated supports shall take account of the effects of: (a)changes in ground water level, (b)water, weather and vegetation, and (c)ground loss and slumping. |
Clause B2—Durability
| Provisions | Limits on application |
|---|---|
Objective |
|
B2.1The objective of this provision is to ensure that a building will throughout its life continue to satisfy the other objectives of this code. |
|
Functional requirement |
|
B2.2Building materials, components and construction methods shall be sufficiently durable to ensure that the building, without reconstruction or major renovation, satisfies the other functional requirements of this code throughout the life of the building. |
|
Performance |
|
B2.3[Revoked] |
|
B2.3.1Building elements must, with only normal maintenance, continue to satisfy the performance requirements of this code for the lesser of the specified intended life of the building, if stated, or: (a)the life of the building, being not less than 50 years, if: (i)those building elements (including floors, walls, and fixings) provide structural stability to the building, or (ii)those building elements are difficult to access or replace, or (iii)failure of those building elements to comply with the building code would go undetected during both normal use and maintenance of the building. (b)15 years if: (i)those building elements (including the building envelope, exposed plumbing in the subfloor space, and in-built chimneys and flues) are moderately difficult to access or replace, or (ii)failure of those building elements to comply with the building code would go undetected during normal use of the building, but would be easily detected during normal maintenance. (c)5 years if: (i)the building elements (including services, linings, renewable protective coatings, and fixtures) are easy to access and replace, and (ii)failure of those building elements to comply with the building code would be easily detected during normal use of the building. |
Performance B2.3.1 applies from the time of issue of the applicable code compliance certificate. Building elements are not required to satisfy a durability performance which exceeds the specified intended life of the building. |
B2.3.2Individual building elements which are components of a building system and are difficult to access or replace must either: (a)all have the same durability, or (b)be installed in a manner that permits the replacement of building elements of lesser durability without removing building elements that have greater durability and are not specifically designed for removal and replacement. |
Schedule 1 clause B2.3: revoked, on 11 September 1997, by regulation 2 of the Building Amendment Regulations 1997 (SR 1997/156).
Schedule 1 clause B2.3.1: added, on 11 September 1997, by regulation 2 of the Building Amendment Regulations 1997 (SR 1997/156).
Schedule 1 clause B2.3.2: added, on 11 September 1997, by regulation 2 of the Building Amendment Regulations 1997 (SR 1997/156).
Clause C1—Outbreak of fire
| Provisions | Limits on application |
|---|---|
Objective |
|
C1.1The objective of this provision is to safeguard people from injury or illness caused by fire. |
|
Functional requirement |
|
C1.2In buildings fixed appliances using the controlled combustion of solid, liquid or gaseous fuel, shall be installed in a way which reduces the likelihood of fire. |
|
Performance |
|
C1.3.1Fixed appliances and services shall be installed so as to avoid the accumulation of gases within the installation and in building spaces, where heat or ignition could cause uncontrolled combustion or explosion. |
|
C1.3.2Fixed appliances shall be installed in a manner that does not raise the temperature of any building element by heat transfer or concentration to a level that would adversely affect its physical or mechanical properties or function. |
Clause C2—Means of escape
| Provisions | Limits on application |
|---|---|
Objective |
|
C2.1The objective of this provision is to: (a)safeguard people from injury or illness from a fire while escaping to a safe place, and (b)facilitate fire rescue operations. |
|
Functional requirement |
|
C2.2Buildings shall be provided with means of escape from fire which: (a)give people adequate time to reach a safe place without being overcome by the effects of fire, and (b)give fire service personnel adequate time to undertake rescue operations. |
|
Performance |
|
C2.3.1The number of open paths available to each person escaping to an exitway or final exit shall be appropriate to: (a)the travel distance. (b)the number of occupants, (c)the fire hazard, and (d)the fire safety systems installed in the firecell. |
|
C2.3.2The number of exitways or final exits available to each person shall be appropriate to: (a)the open path travel distance, (b)the building height, (c)the number of occupants, (d)the fire hazard, and (e)the fire safety systems installed in the building. |
|
C2.3.3Escape routes shall be: (a)of adequate size for the number of occupants, (b)free of obstruction in the direction of escape, (c)of length appropriate to the mobility of the people using them, (d)resistant to the spread of fire as required by Clause C3 Spread of fire, (e)easy to find as required by Clause F8 Signs, (f)provided with systems for visibility during failure of the main lighting, as required by Clause F6 Visibility in escape routes, and (g)easy and safe to use as required by Clause D1.3.3 Access routes. |
Performance C2.3.3(b) must not prevent a door that forms part of an escape route from being locked if the person who locks it is satisfied that no one is in that part of the building served by the escape route and that no one is likely to enter that part of the building, except in an emergency, without unlocking that door. |
Schedule 1 clause C2.2: amended, on 3 January 2002, by regulation 3(1) of the Building Amendment Regulations 2001 (SR 2001/374).
Schedule 1 clause C2.3.3(b) limit on application: amended, on 3 January 2002, by regulation 3(2) of the Building Amendment Regulations 2001 (SR 2001/374).
Schedule 1 clause C2.3.3(f): substituted, on 21 June 2007, by regulation 6(3) of the Building Amendment Regulations 2007 (SR 2007/124).
Clause C3—Spread of fire
| Provisions | Limits on application |
|---|---|
Objective |
|
C3.1The objective of this provision is to: (a)safeguard people from injury or illness when evacuating a building during fire. (b)provide protection to fire service personnel during firefighting operations. (c)protect adjacent household units, other residential units, and other property from the effects of fire. (d)safeguard the environment from adverse effects of fire. |
|
Functional requirement |
|
C3.2Buildings shall be provided with safeguards against fire spread so that: (a)occupants have time to escape to a safe place without being overcome by the effects of fire, (b)firefighters may undertake rescue operations and protect property, (c)adjacent household units, other residential units, and other property are protected from damage, and (d)significant quantities of hazardous substances are not released to the environment during fire. |
Requirement C3.2(d) applies only to buildings where significant quantities of hazardous substances are stored or processed. |
Performance |
|
C3.3.1Interior surface finishes on walls, floors, ceilings and suspended building elements, shall resist the spread of fire and limit the generation of toxic gases, smoke and heat, to a degree appropriate to: (a)the travel distance, (b)the number of occupants, (c)the fire hazard, and (d)the active fire safety systems installed in the building. |
|
C3.3.2Fire separations shall be provided within buildings to avoid the spread of fire and smoke to: (a)other firecells, (b)spaces intended for sleeping, and (c)household units within the same building or adjacent buildings. (d)other property. |
Performance C3.3.2(b) does not apply to detached dwellings or within household units of multi-unit dwellings. |
C3.3.3Fire separations shall: (a)where openings occur, be provided with fire resisting closures to maintain the integrity of the fire separations for an adequate time, and (b)where penetrations occur, maintain the fire resistance rating of the fire separation. |
|
C3.3.4Concealed spaces and cavities within buildings shall be sealed and subdivided where necessary to inhibit the unseen spread of fire and smoke. |
Performance C3.3.4 shall not apply to detached dwellings. |
C3.3.5External walls and roofs shall have resistance to the spread of fire, appropriate to the fire load within the building and to the proximity of other household units, other residential units, and other property. |
|
C3.3.6Automatic fire suppression systems shall be installed where people would otherwise be: (a)unlikely to reach a safe place in adequate time because of the number of storeys in the building, (b)required to remain within the building without proceeding directly to a final exit, or where the evacuation time is excessive, (c)unlikely to reach a safe place due to confinement under institutional care because of mental or physical disability, illness or legal detention, and the evacuation time is excessive, or (d)at high risk due to the fire load and fire hazard within the building. |
|
C3.3.7Air conditioning and mechanical ventilation systems shall be constructed to avoid circulation of smoke and fire between firecells. |
|
C3.3.8Where an automatic smoke control system is installed, it shall be constructed to: (a)avoid the spread of fire and smoke between firecells, and (b)protect escape routes from smoke until the occupants have reached a safe place. |
|
C3.3.9The fire safety systems installed shall facilitate the specific needs of fire service personnel to: (a)carry out rescue operations, and (b)control the spread of fire. |
Performance C3.3.9 does not apply to backcountry huts. |
C3.3.10Environmental protection systems shall ensure a low probability of hazardous substances being released to: (a)soils, vegetation or natural waters, (b)the atmosphere, and (c)sewers or public drains. |
Performance C3.3.10 applies only to buildings where significant quantities of hazardous substances are stored or processed. |
Schedule 1 clause C3.1(c): amended, on 3 January 2002, by regulation 3(3) of the Building Amendment Regulations 2001 (SR 2001/374).
Schedule 1 clause C3.2(c): amended, on 3 January 2002, by regulation 3(4) of the Building Amendment Regulations 2001 (SR 2001/374).
Schedule 1 clause C3.3.2 limit on application: revoked, on 3 January 2002, by regulation 3(5)(b) of the Building Amendment Regulations 2001 (SR 2001/374).
Schedule 1 clause C3.3.2(b) limit on application: inserted, on 3 January 2002, by regulation 3(5)(c) of the Building Amendment Regulations 2001 (SR 2001/374).
Schedule 1 clause C3.3.2(d): added, on 3 January 2002, by regulation 3(5)(a) of the Building Amendment Regulations 2001 (SR 2001/374).
Schedule 1 clause C3.3.5: amended, on 3 January 2002, by regulation 3(6) of the Building Amendment Regulations 2001 (SR 2001/374).
Schedule 1 clause C3.3.9 limit on application: inserted, on 31 October 2008, by regulation 6 of the Building (Building Code: Backcountry Huts) Amendment Regulations 2008 (SR 2008/358).
Clause C4—Structural stability during fire
| Provisions | Limits on application |
|---|---|
Objective |
|
C4.1The objective of this provision is to: (a)safeguard people from injury due to loss of structural stability during fire, and (b)protect household units and other property from damage due to structural instability caused by fire. |
|
Functional requirement |
|
C4.2Buildings shall be constructed to maintain structural stability during fire to: (a)allow people adequate time to evacuate safely, (b)allow fire service personnel adequate time to undertake rescue and firefighting operations, and (c)avoid collapse and consequential damage to adjacent household units or other property. |
|
Performance |
|
C4.3.1Structural elements of buildings shall have fire resistance appropriate to the function of the elements, the fire load, the fire intensity, the fire hazard, the height of the buildings and the fire control facilities external to and within them. |
|
C4.3.2Structural elements shall have a fire resistance of no less than that of any element to which they provide support within the same firecell. |
|
C4.3.3Collapse of elements having lesser fire resistance shall not cause the consequential collapse of elements required to have a higher fire resistance. |
Clause D1—Access routes
| Provisions | Limits on application |
|---|---|
Objective |
|
D1.1The objective of this provision is: (a)safeguard people from injury during movement into, within and out of buildings, (b)safeguard people from injury resulting from the movement of vehicles into, within and out of buildings, and (c)ensure that people with disabilities are able to enter and carry out normal activities and functions within buildings. |
Objective D1.1(c) shall apply only to those buildings to which section 47A of the Act applies. |
Functional requirement |
|
D1.2.1Buildings shall be provided with reasonable and adequate access to enable safe and easy movement of people. |
Requirement D1.2.1 shall not apply to ancillary buildings or outbuildings. |
D1.2.2Where a building is provided with loading or parking spaces, they shall be constructed to permit safe and easy unloading and movement of vehicles, and to avoid conflict between vehicles and pedestrians. |
|
Performance |
|
D1.3.1Access routes shall enable people to: (a)safely and easily approach the main entrance of buildings from the apron or construction edge of a building, (b)enter buildings, (c)move into spaces within buildings by such means as corridors, doors, stairs, ramps and lifts, (d)manoeuvre and park cars, and (e)manoeuvre and park delivery vehicles required to use the loading space. |
|
D1.3.2At least one access route shall have features to enable people with disabilities to: (a)approach the building from the street boundary or, where required to be provided, the building car park, (b)have access to the internal space served by the principal access, and (c)have access to and within those spaces where they may be expected to work or visit, or which contain facilities for personal hygiene as required by Clause G1 Personal hygiene. |
Performance D1.3.2 shall not apply to housing, outbuildings, backcountry huts, ancillary buildings, and to industrial buildings where no more than 10 people are employed. |
D1.3.3Access routes shall: (a)have adequate activity space, (b)be free from dangerous obstructions and from any projections likely to cause an obstruction, (c)have a safe cross fall, and safe slope in the direction of travel, (d)have adequate slip-resistant walking surfaces under all conditions of normal use, (e)include stairs to allow access to upper floors irrespective of whether an escalator or lift has been provided, (f)have stair treads, and ladder treads or rungs which: (i)provide adequate footing, and (ii)have uniform rise within each flight and for consecutive flights, (g)have stair treads with a leading edge that can be easily seen, (h)have stair treads which prevent children falling through or becoming held fast between treads, where open risers are used, (i)not contain isolated steps, (j)have smooth, reachable and graspable handrails to provide support and to assist with movement along a stair or ladder, (k)have handrails of adequate strength and rigidity as required by Clause B1 Structure, (l)have landings of appropriate dimensions and at appropriate intervals along a stair or ramp to prevent undue fatigue, (m)have landings of appropriate dimensions where a door opens from or onto a stair, ramp or ladder so that the door does not create a hazard, and (n)have any automatically controlled doors constructed to avoid the risk of people becoming caught or being struck by moving parts. |
Performance D1.3.3(h) shall not apply within industrial buildings, outbuildings and ancillary buildings. Performance D1.3.3(i) shall not apply with detached dwellings or within household units of multi-unit dwellings, or to outbuildings and ancillary buildings. Performance D1.3.3(j) shall not apply to isolated steps. |
D1.3.4An accessible route, in addition to the requirement of Clause D1.3.3, shall: (a)be easy to find, as required by Clause F8 Signs, (b)have adequate activity space to enable a person in a wheelchair to negotiate the route while permitting an ambulant person to pass, (c)include a lift complying with Clause D2 Mechanical installations for access to upper floors where: (i)buildings are four or more storeys high, (ii)buildings are three storeys high and have a total design occupancy of 50 or more persons on the two upper floors, (iii)buildings are two storeys high and have a total design occupancy of 40 or more persons on the upper floor, or (iv)an upper floor, irrespective of design occupancy, is to be used for the purposes of public reception areas of banks, central, regional and local government offices and facilities, hospitals, medical and dental surgeries, and medical, paramedical and other primary health care centres, (d)contain no thresholds or upstands forming a barrier to an unaided wheelchair user, (e)have means to prevent the wheel of a wheelchair dropping over the side of the accessible route, (f)have doors and related hardware which are easily used, (g)not include spiral stairs, or stairs having open risers, (h)have stair treads with leading edge which is rounded, and (i)have handrails on both sides of the accessible route when the slope of the route exceeds 1 in 20. The handrails shall be continuous along both sides of the stair, ramp and landing except where the handrail is interrupted by a doorway. |
|
D1.3.5Vehicle spaces and circulation routes shall have: (a)dimensions appropriate to the intended use, (b)appropriate crossfall, and slope in the direction of travel, (c)adequate queuing and circulation space, and (d)adequate sight distances. |
|
D1.3.6Vehicle spaces for use by people with disabilities, shall, in addition to the requirements of Clause D1.3.5, be: (a)provided in sufficient numbers, (b)located to avoid conflict between vehicles and people using or moving to or from the space, and (c)easy to find as required by Clause F8 Signs. |
Schedule 1 clause D1.1(c) limit on application: amended, on 29 December 2000, by regulation 4(1) of the Building Amendment Regulations 2000 (SR 2000/119).
Schedule 1 clause D1.3.2 limit on application: amended, on 31 October 2008, by regulation 7 of the Building (Building Code: Backcountry Huts) Amendment Regulations 2008 (SR 2008/358).
Clause D2—Mechanical installations for access
| Provisions | Limits on application |
|---|---|
Objective |
|
D2.1The objective of this provision is to: (a)safeguard people from injury and loss of amenity while using mechanical installations for movement into, within and out of buildings, (b)safeguard maintenance personnel from injury while servicing mechanical installations for access, and (c)ensure that people with disabilities are able to carry out normal activities and processes within buildings. |
Objective D2.1(c) shall apply only to those buildings to which section 47A of the Act applies. |
Functional requirement |
|
D2.2Mechanical installations for access into, within and out of buildings shall provide for the safe and easy movement of people, and for the safety of maintenance personnel. |
|
Performance |
|
D2.3.1Mechanical installations for access shall: (a)move people safely, and stop and hold as required for the normal use of the installation, for all loads up to and including 25% in excess of the rated load, (b)not produce excessive acceleration or deceleration, (c)be constructed to avoid the likelihood of people falling, tripping, becoming caught, being able to touch or be struck by moving parts, sharp edges or projections, under both normal and reasonably foreseeable abnormal conditions of use, (d)be constructed to prevent collision between components, or between components and the building, (e)have a control system that ensures safe abnormal operation in the event of overloading or failure of any single component, and (f)be capable of being isolated for inspection, testing and maintenance. |
|
D2.3.2Mechanical installations for access shall be provided with: (a)adequate control over normal use, to ensure people’s safety throughout any operation involving starting, stopping or changing the direction of travel, (b)notification of position, where people are fully enclosed and the installation serves more than two levels, (c)adequate lighting and ventilation for both normal and emergency use, and (d)signs as required by Clause F8 Signs. |
|
D2.3.3Mechanical installations for access shall, for emergency purposes, be provided with a means of: (a)calling outside help, (b)releasing people safely, (c)safeguarding people from exposure to hazardous situations, and (d)allowing authorised personnel to override the normal running procedure and take exclusive control of the installation. |
Performance D2.3.3(d) shall not apply to installations travelling less than 15 m vertically. |
D2.3.4Potentially dangerous equipment shall be located in spaces which: (a)are secure from unauthorised entry and contain only equipment associated with the installation, (b)are appropriately sized and suitably guarded to provide adequate safe working areas for maintenance personnel, (c)are provided with adequate power and lighting for maintenance, and (d)have an environment that ensures the safe operation of the equipment under all likely conditions of use. |
|
D2.3.5Mechanical installations on accessible routes shall: (a)where the passenger conveyor is manually controlled, provide: (i)controls which are easily identifiable and easy to use, (ii)adequate notification that the passenger conveyor has registered a summoning call, and (iii)adequate notification that the passenger conveyor has arrived, and of its future direction of travel, (b)where the passenger conveyor is fully enclosed and serves more than two levels, provide an adequate means of informing occupants of their location, (c)where appropriate, have doors which: (i)are power operated, (ii)are readily distinguishable from their surroundings, and (iii)where automatic, remain open sufficiently long to enable people with disabilities to pass through, and (d)have handrails within the passenger conveyor. |
Schedule 1 clause D2.1(c) limit on application: amended, on 29 December 2000, by regulation 4(1) of the Building Amendment Regulations 2000 (SR 2000/119).
Clause E1—Surface water
| Provisions | Limits on application |
|---|---|
Objective |
|
E1.1The objective of this provision is to: (a)safeguard people from injury or illness, and other property from damage, caused by surface water, and (b)protect the outfalls of drainage systems. |
|
Functional requirement |
|
E1.2Buildings and sitework shall be constructed in a way that protects people and other property from the adverse effects of surface water. |
|
Performance |
|
E1.3.1Except as otherwise required under the Resource Management Act 1991 for the protection of other property, surface water, resulting from an event having a 10% probability of occurring annually and which is collected or concentrated by buildings or sitework, shall be disposed of in a way that avoids the likelihood of damage or nuisance to other property. |
|
E1.3.2Surface water, resulting from an event having a 2% probability of occurring annually, shall not enter buildings. |
Performance E1.3.2 shall apply only to housing, communal residential and communal non-residential buildings. |
E1.3.3Drainage systems for the disposal of surface water shall be constructed to: (a)convey surface water to an appropriate outfall using gravity flow where possible, (b)avoid the likelihood of blockages, (c)avoid the likelihood of leakage, penetration by roots, or the entry of ground water where pipes or lined channels are used, (d)provide reasonable access for maintenance and clearing blockages, (e)avoid the likelihood of damage to any outfall, in a manner acceptable to the network utility operator, and (f)avoid the likelihood of damage from superimposed loads or normal ground movements. |
Schedule 1 clause E1.3.1: amended, on 3 January 2002, by regulation 3(7) of the Building Amendment Regulations 2001 (SR 2001/374).
Schedule 1 clause E1.3.1: amended, on 22 December 1994, by regulation 4 of the Building Regulations 1992, Amendment No 1 (SR 1994/263).
Schedule 1 clause E1.3.2: amended, on 3 January 2002, by regulation 3(8) of the Building Amendment Regulations 2001 (SR 2001/374).
Clause E2—External moisture
| Provisions | Limits on application |
|---|---|
Objective |
|
E2.1The objective of this provision is to safeguard people from illness or injury that could result from external moisture entering the building. |
|
Functional requirement |
|
E2.2Buildings must be constructed to provide adequate resistance to penetration by, and the accumulation of, moisture from the outside. |
Requirement E2.2 does not apply to buildings (for example, certain bus shelters, and certain buildings used for horticulture or for equipment for washing motor vehicles automatically) if moisture from the outside penetrating them, or accumulating within them, or both, is unlikely to impair significantly all or any of their amenity, durability, and stability. |
Performance |
|
E2.3.1Roofs must shed precipitated moisture. In locations subject to snowfalls, roofs must also shed melted snow. |
|
E2.3.2Roofs and exterior walls must prevent the penetration of water that could cause undue dampness, damage to building elements, or both. |
|
E2.3.3Walls, floors, and structural elements in contact with, or in close proximity to, the ground must not absorb or transmit moisture in quantities that could cause undue dampness, damage to building elements, or both. |
|
E2.3.4Building elements susceptible to damage must be protected from the adverse effects of moisture entering the space below suspended floors. |
|
E2.3.5Concealed spaces and cavities in buildings must be constructed in a way that prevents external moisture being accumulated or transferred and causing condensation, fungal growth, or the degradation of building elements. |
|
E2.3.6Excess moisture present at the completion of construction must be capable of being dissipated without permanent damage to building elements. |
|
E2.3.7Building elements must be constructed in a way that makes due allowance for the following: (a)the consequences of failure: (b)the effects of uncertainties resulting from construction or from the sequence in which different aspects of construction occur: (c)variation in the properties of materials and in the characteristics of the site. |
Schedule 1 clause E2: substituted, on 21 June 2007, by regulation 4 of the Building Amendment Regulations 2007 (SR 2007/124).
Clause E3—Internal moisture
| Provisions | Limits on application |
|---|---|
Objective |
|
E3.1The objective of this provision is to— (a)safeguard people against illness, injury, or loss of amenity that could result from accumulation of internal moisture; and (b)protect household units and other property from damage caused by free water from another household unit in the same building. |
|
Functional requirement |
|
E3.2Buildings must be constructed to avoid the likelihood of— (a)fungal growth or the accumulation of contaminants on linings and other building elements; and (b)free water overflow penetrating to an adjoining household unit; and (c)damage to building elements caused by the presence of moisture. |
|
Performance |
|
E3.3.1An adequate combination of thermal resistance, ventilation, and space temperature must be provided to all habitable spaces, bathrooms, laundries, and other spaces where moisture may be generated or may accumulate. |
Performance E3.3.1 does not apply to communal non-residential, commercial, industrial, outbuildings, or ancillary buildings. |
E3.3.2Free water from accidental overflow from sanitary fixtures or sanitary appliances must be disposed of in a way that avoids loss of amenity or damage to household units or other property. |
|
E3.3.3Floor surfaces of any space containing sanitary fixtures or sanitary appliances must be impervious and easily cleaned. |
|
E3.3.4Wall surfaces adjacent to sanitary fixtures or sanitary appliances must be impervious and easily cleaned. |
|
E3.3.5Surfaces of building elements likely to be splashed or become contaminated in the course of the intended use of the building, must be impervious and easily cleaned. |
|
E3.3.6Surfaces of building elements likely to be splashed must be constructed in a way that prevents water splash from penetrating behind linings or into concealed spaces. |
Schedule 1 clause E3: substituted, on 14 October 2004, by regulation 3 of the Building Amendment Regulations 2004 (SR 2004/317).
Clause F1—Hazardous agents on site
| Provisions | Limits on application |
|---|---|
Objective |
|
F1.1The objective of this provision is to safeguard people from injury or illness caused by hazardous agents or contaminants on a site. |
|
Functional requirement |
|
F1.2Buildings shall be constructed to avoid the likelihood of people within the building being adversely affected by hazardous agents or contaminants on the site. |
|
Performance |
|
F1.3.1Sites shall be assessed to determine the presence and potential threat of any hazardous agents or contaminants. |
|
F1.3.2The likely effect of any hazardous agent or contaminant on people shall be determined taking account of: (a)the intended use of the building, (b)the nature, potency or toxicity of the hazardous agent or contaminant, and (c)the protection afforded by the building envelope and building systems. |
Clause F2—Hazardous building materials
| Provisions | Limits on application |
|---|---|
Objective |
|
F2.1The objective of this provision is to safeguard people from injury and illness caused by exposure to hazardous building materials. |
|
Functional requirement |
|
F2.2Building materials which are potentially hazardous, shall be used in ways that avoid undue risk to people. |
|
Performance |
|
F2.3.1The quantities of gas, liquid, radiation or solid particles emitted by materials used in the construction of buildings, shall not give rise to harmful concentrations at the surface of the material where the material is exposed, or in the atmosphere of any space. |
|
F2.3.2Transparent panels capable of being mistaken for an unimpeded path of travel shall be marked to make them visible. |
Performance F2.3.2 does not apply to housing |
F2.3.3Glass or other brittle materials with which people are likely to come into contact shall: (a)if broken on impact, break in a way which is unlikely to cause injury, or (b)resist a reasonably foreseeable impact without breaking, or (c)be protected from impact. |
Clause F3— Hazardous substances and processes
| Provisions | Limits on application |
|---|---|
Objective |
|
F3.1The objective of this provision is to safeguard people from injury or illness, and other property from damage, caused by hazardous substances or processes in buildings. |
|
Functional requirement |
|
F3.2Buildings where hazardous substances are stored and hazardous processes undertaken, shall be constructed to provide adequate protection to people and to other property. |
|
Performance |
|
F3.3Spaces in buildings where hazardous substances are stored, handled or used, or where hazardous processes are undertaken, shall be located and constructed to protect people, and other property, under both normal and reasonably foreseeable abnormal conditions, and shall be provided with: (a)means of restricting unauthorised access, (b)means of preventing hazardous substances, or other materials unacceptable to the network utility operator, from entering sewers or public drains, (c)means of allowing the harmless release of pressure where there is a significant risk of explosion occurring, (d)protected ignition sources where flammable or explosive goods are stored, (e)means of rendering harmless by ventilation, containment, dilution, or chemical or biological action, any radioactive, toxic or flammable vapours, gases or materials which may escape from pipes, vessels or containers, (f)impervious, easily cleaned surface finishes on building elements likely to be splashed or become contaminated in the course of the intended use of the building, and (g)signs as required by Clause F8 Signs. |
Clause F4—Safety from falling
| Provisions | Limits on application |
|---|---|
Objective |
|
F4.1The objective of this provision is to safeguard people from injury caused by falling. |
|
Functional requirement |
|
F4.2Buildings shall be constructed to reduce the likelihood of accidental fall. |
|
Performance |
|
F4.3.1Where people could fall 1 metre or more from an opening in the external envelope or floor of a building, or from a sudden change of level within or associated with a building, a barrier shall be provided. |
Performance F4.3.1 shall not apply where such a barrier would be incompatible with the intended use of an area, or to temporary barriers on construction sites where the possible fall is less than 3 metres, or to buildings providing pedestrian access in remote locations where the route served presents similar natural hazards. |
F4.3.2Roofs with permanent access shall have barriers provided. |
|
F4.3.3Swimming pools having a depth of water exceeding 400 mm, shall have barriers provided. |
Performance F4.3.3 shall not apply to any pool exempted under section 5 of the Fencing of Swimming Pools Act 1987. |
F4.3.4Barriers shall: (a)be continuous and extend for the full extent of the hazard, (b)be of appropriate height, (c)be constructed with adequate rigidity, (d)be of adequate strength to withstand the foreseeable impact of people and, where appropriate, the static pressure of people pressing against them, (e)be constructed to prevent people from falling through them, and (f)in the case of a swimming pool, restrict the access of children under 6 years of age to the pool or the immediate pool area. (g)restrict the passage of children under 6 years of age when provided to guard a change of level in areas likely to be frequented by them. (h)be constructed so that they are not readily able to be used as seats. |
Performance F4.3.4(f) shall not apply to any pool exempted under section 5 of the Fencing of Swimming Pools Act 1987. Performance F4.3.4(h) does not apply to housing. |
F4.3.5Barriers to swimming pools shall have in addition to performance F4.3.4: (a)all gates and doors fitted with latching devices not readily operated by children, and constructed to automatically close and latch when released from any stationary position 150 mm or more from the closed and secured position, but excluding sliding and sliding-folding doors that give access to the immediate pool surround from a building that forms part of the barrier, and (b)no permanent objects on the outside of the barrier that could provide a climbing step. |
Schedule 1 clause F4.3.1 limit on application: amended, on 3 January 2002, by regulation 3(9) of the Building Amendment Regulations 2001 (SR 2001/374).
Schedule 1 clause F4.3.3: amended, on 22 December 1994, by regulation 5(1) of the Building Regulations 1992, Amendment No 1 (SR 1994/263).
Schedule 1 clause F4.3.4(f): substituted, on 22 December 1994, by regulation 5(2)(a) of the Building Regulations 1992, Amendment No 1 (SR 1994/263).
Schedule 1 clause F4.3.4(f) limit on application: inserted, on 22 December 1994, by regulation 5(2)(b) of the Building Regulations 1992, Amendment No 1 (SR 1994/263).
Schedule 1 clause F4.3.4(g): added, on 22 December 1994, by regulation 5(2)(c) of the Building Regulations 1992, Amendment No 1 (SR 1994/263).
Schedule 1 clause F4.3.4(h): added, on 21 June 2007, by regulation 5 of the Building Amendment Regulations 2007 (SR 2007/124).
Schedule 1 clause F4.3.5(a): substituted, on 22 December 1994, by regulation 5(3) of the Building Regulations 1992, Amendment No 1 (SR 1994/263).
Clause F5—Construction and demolition hazards
| Provisions | Limits on application |
|---|---|
Objective |
|
F5.1The objective of this provision is to safeguard people from injury, and other property from damage, caused by construction or demolition site hazards. |
|
Functional requirement |
|
F5.2Construction and demolition work on buildings shall be performed in a manner that avoids the likelihood of: (a)objects falling onto people on or off the site, (b)objects falling on property off the site, (c)other hazards arising on the site affecting people off the site and other property, and (d)unauthorised entry of children to hazards on the site. |
|
Performance |
|
F5.3.1Suitable construction methods shall be used to avoid the likelihood of tools or materials falling onto places where people might be present. |
|
F5.3.2Where construction or demolition work presents a hazard in places to which the public has access, barriers shall be provided and shall: (a)be of appropriate height and construction to prevent site hazards from harming traffic or passersby, (b)be difficult to climb, (c)have no opening other than those approved by the territorial authority for access and viewing, (d)have no gates or doors which project beyond the site when opened, (e)contain no projection that would be a hazard to traffic or people, and (f)be clearly marked where the barrier itself may otherwise present a hazard to traffic or passersby. |
|
F5.3.3Where a construction or demolition site contains any hazard which might be expected to attract the unauthorised entry of children, the hazard shall be enclosed to restrict access by children. |
|
F5.3.4Suitable barriers shall be constructed to provide a safe route for people where lifting equipment creates a risk of accident from objects falling on a place of public access, or where a similar risk results from the height at which construction or demolition work is being carried out. |
Schedule 1 second clause F5 number: revoked, on 22 December 1994, by regulation 6 of the Building Regulations 1992, Amendment No 1 (SR 1994/263).
Schedule 1 clause F5.2 number: inserted, on 22 December 1994, by regulation 6 of the Building Regulations 1992, Amendment No 1 (SR 1994/263).
Clause F6—Visibility in escape routes
| Provisions | Limits on application |
|---|---|
Objective |
|
F6.1The objective of this provision is to help safeguard people from injury in escape routes during failure of the main lighting. |
|
Functional requirement |
|
F6.2Specified features in escape routes must be made reasonably visible by lighting systems, other systems, or both, during failure of the main lighting. |
Requirement F6.2 does not apply to detached dwellings, household units within multi-unit dwellings, outbuildings, backcountry huts, or ancillary buildings. |
Performance |
|
F6.3.1Specified features in escape routes must, when the systems for visibility are at their design level, be reasonably visible. |
Performance F6.3.1 does not apply to specified features in the initial 20 metres of an escape route if the risk of injury, or impediment to movement of people, due to the specified features not being visible is low (for example, because people are familiar with the escape route, the escape route is level, and people do not require assistance to escape). |
F6.3.2The systems for visibility must operate to the following percentages of their design levels within the following times after failure of the main lighting: (a)80% in 0.5 seconds in locations (examples of which are given by performance F6.3.3) where there is a high risk of injury due to delay in operation of the systems for visibility; and (b)10% in 0.5 seconds, and 80% in 30 seconds, in stairs and in locations that are unfamiliar to users; and (c)10% in 20 seconds, and 80% in 60 seconds, in all other locations. |
|
F6.3.3Examples of locations (referred to in performance F6.3.2(a)) where there is a high risk of injury due to delay in operation of the systems for visibility include: (a)areas where dangerous machinery is installed: (b)areas where hazardous processes take place: (c)clinical areas of hospitals: (d)prisons and other buildings in which people are detained: (e)any part of an escape route designed for use at any time by more than 250 people. |
|
F6.3.4The systems for visibility must operate continuously in buildings or parts of buildings in the following risk groups for the following periods after failure of the main lighting: (a)risk group A, until restoration of the main lighting system: (b)risk group B, 90 minutes: (c)risk group C, 30 minutes. |
|
F6.3.5Despite performance F6.3.4, if a building or part of a building falls into both risk group A and risk group B, the systems for visibility must operate for whichever is the longer of the periods specified in performance F6.3.4(a) and (b). |
|
F6.3.6Signs to indicate escape routes must be provided as required by Clause F8 Signs. |
Schedule 1 clause F6: substituted, on 21 June 2007, by regulation 6(1) of the Building Amendment Regulations 2007 (SR 2007/124).
Schedule 1 clause F6.2 limit on application: amended, on 31 October 2008, by regulation 8 of the Building (Building Code: Backcountry Huts) Amendment Regulations 2008 (SR 2008/358).
Clause F7—Warning systems
| Provisions | Limits on application |
|---|---|
Objective |
|
F7.1The objective of this provision is to safeguard people from injury or illness due to lack of awareness of an emergency. |
|
Functional requirement |
|
F7.2Buildings shall be provided with appropriate means of warning people to escape to a safe place in an emergency. |
|
Performance |
|
F7.3[Revoked] |
|
F7.3.1A means of warning must alert people to the emergency in adequate time for them to reach a safe place. |
Performance F7.3 does not apply to outbuildings, backcountry huts, or ancillary buildings. |
F7.3.2Appropriate means of detection and warning for fire must be provided within each household unit. |
|
F7.3.3Appropriate means of warning for fire and other emergencies must be provided in buildings as necessary to satisfy the other performance requirements of this code. |
Schedule 1 clause F7.2: amended, on 24 April 2003, by regulation 3(1) of the Building Amendment Regulations 2003 (SR 2003/61).
Schedule 1 clause F7.3: revoked, on 24 April 2003, by regulation 3(2) of the Building Amendment Regulations 2003 (SR 2003/61).
Schedule 1 clause F7.3.1: added, on 24 April 2003, by regulation 3(2) of the Building Amendment Regulations 2003 (SR 2003/61).
Schedule 1 clause F7.3.1 limit on application: amended, on 31 October 2008, by regulation 9 of the Building (Building Code: Backcountry Huts) Amendment Regulations 2008 (SR 2008/358).
Schedule 1 clause F7.3.2: added, on 24 April 2003, by regulation 3(2) of the Building Amendment Regulations 2003 (SR 2003/61).
Schedule 1 clause F7.3.3: added, on 24 April 2003, by regulation 3(2) of the Building Amendment Regulations 2003 (SR 2003/61).
Clause F8—Signs
| Provisions | Limits on application |
|---|---|
Objective |
|
F8.1The objective of this provision is to: (a)safeguard people from injury or illness resulting from inadequate identification of escape routes, or of hazards within or about the building, (b)safeguard people from loss of amenity due to inadequate direction, and (c)ensure that people with disabilities are able to carry out normal activities and processes within buildings. |
Objective F8.1(c) shall apply only to those buildings to which section 47A of the Act applies. |
Functional requirement |
|
F8.2Signs shall be provided in and about buildings to identify: (a)escape routes, (b)emergency related safety features, (c)potential hazards, and (d)accessible routes and facilities for people with disabilities. |
Requirement F8.2 shall not apply to detached dwellings, or within household units of multi-unit dwellings. |
Performance |
|
F8.3.1Signs shall be clearly visible and readily understandable under all conditions of foreseeable use. |
|
F8.3.2Signs indicating potential hazards shall be provided in sufficient locations to notify people before they encounter the hazard. |
|
F8.3.4Signs shall be provided in sufficient locations to identify accessible routes and facilities provided for people with disabilities. |
Schedule 1 clause F8.1(c) limit on application: amended, on 29 December 2000, by regulation 4(1) of the Building Amendment Regulations 2000 (SR 2000/119).
Schedule 1 clause F8.3.3(b): substituted, on 21 June 2007, by regulation 6(4) of the Building Amendment Regulations 2007 (SR 2007/124).
Clause G1—Personal hygiene
| Provisions | Limits on application |
|---|---|
| Objective | |
G1.1The objective of this provision is to: (a)safeguard people from illness caused by infection or contamination, (b)safeguard people from loss of amenity arising from the absence of appropriate personal hygiene facilities, and (c)ensure people with disabilities are able to carry out normal activities and processes within buildings. |
Objective G1.1(c) shall apply only to those buildings to which section 47A of the Act applies. |
Functional requirement |
|
G1.2Buildings shall be provided with appropriate spaces and facilities for personal hygiene. |
|
Performance |
|
G1.3.1Sanitary fixtures shall be provided in sufficient number and be appropriate for the people who are intended to use them. |
|
G1.3.2Sanitary fixtures shall be located, constructed and installed to: (a)facilitate sanitation, (b)avoid risk of food contamination, (c)avoid harbouring dirt or germs, (d)provide appropriate privacy, (e)avoid affecting occupants of adjacent spaces from the presence of unpleasant odours, accumulation of offensive matter, or other source of annoyance, (f)allow effective cleaning, (g)discharge to a plumbing and drainage system as required by Clause G13 Foul water when water-borne disposal is used, and (h)provide a healthy safe disposal system when non-water-borne disposal is used. |
|
G1.3.3Facilities for personal hygiene shall be provided in convenient locations. |
|
G1.3.4Personal hygiene facilities provided for people with disabilities shall be accessible. |
Performance G1.3.4 shall not apply to housing, outbuildings, backcountry huts, ancillary buildings, and to industrial buildings where no more than 10 people are employed. |
Schedule 1 clause G1.1(c) limit on application: amended, on 29 December 2000, by regulation 4(1) of the Building Amendment Regulations 2000 (SR 2000/119).
Schedule 1 clause G1.3.4 limit on application: amended, on 31 October 2008, by regulation 10 of the Building (Building Code: Backcountry Huts) Amendment Regulations 2008 (SR 2008/358).
Clause G2—Laundering
| Provisions | Limits on application |
|---|---|
Objective |
|
G2.1The objective of this provision is to ensure: (a)adequate amenities for people to do laundering, and (b)that people with disabilities are able to carry out normal activities and processes within buildings. |
Objective G2.1(b) shall apply to those buildings to which section 47A of the Act applies. |
Functional requirement |
|
G2.2Buildings shall be provided with adequate space and facilities for laundering. |
Requirement G2.2 shall apply only to housing, old people’s homes, early childhood centres, camping grounds and work camps. |
Performance |
|
G2.3.1Facilities shall have capacity for the intended use, and consist of fixtures, or space and services for appliances. |
|
G2.3.2Space shall be adequate in size to provide for the installation and use of fixtures or appliances. |
|
G2.3.3Space and facilities shall be provided within each accommodation unit or may be grouped elsewhere in a convenient location. |
|
G2.3.4Accessible facilities shall be provided for people with disabilities. |
Performance G2.3.4 shall apply only to camping grounds. |
Schedule 1 clause G2.1(b) limit on application: amended, on 29 December 2000, by regulation 4(1) of the Building Amendment Regulations 2000 (SR 2000/119).
Clause G3—Food preparation and prevention of contamination
| Provisions | Limits on application |
|---|---|
Objective |
|
G3.1The objective of this provision is to: (a)safeguard people from illness due to contamination, (b)enable hygienic food preparation without loss of amenity, and (c)ensure that people with disabilities are able to carry out normal activities and processes within buildings. |
Objective G3.1(c) shall apply only to those buildings to which section 47A of the Act applies. |
Functional requirement |
|
G3.2.1Buildings shall be provided with space and facilities for the hygienic storage, preparation and cooking of food, that are adequate for the intended use of the building. |
Requirement G3.2.1 shall apply to housing, work camps, old people’s homes and early childhood centres, and where appropriate shall also apply to commercial and industrial buildings whose intended uses include the manufacture, preparation, packaging or storage of food. |
G3.2.2Buildings used for the storage, manufacture or processing of food, including animal products, shall be constructed to safeguard the contents from contamination. |
|
G3.2.3Buildings used for the medical treatment of humans or animals, or the reception of dead bodies, shall be constructed to avoid the spread of contamination from the building contents. |
|
Performance |
|
G3.3.1Food preparation facilities shall be hygienic and include: (a)space for a refrigerator, or a perishable food storage area capable of being cooled and protected from vermin and insects, (b)means for food rinsing, utensil washing and waste water disposal, (c)means for cooking food, and (d)space and a surface for food preparation. |
Performance G3.3.1(a) and (b) shall apply to housing, work camps, old people’s homes, early childhood centres and commercial or industrial buildings whose intended uses include the handling of perishable food. Performance G3.3.1(c) shall apply to housing, work camps, old people’s homes and early childhood centres. Performance G3.3.1(d) shall apply to housing, work camps, old people’s homes and early childhood centres. |
G3.3.2Spaces for food preparation and utensil washing shall have: (a)interior linings and work surfaces shall be impervious and easily cleaned, (b)all building elements constructed with materials which are free from hazardous substances which could cause contamination to the building contents, and (c)exposed building elements located and shaped to avoid the accumulation of dirt. |
Performance G3.3.2(b) shall apply to housing, work camps, old people’s homes and early childhood centres, and where appropriate shall also apply to commercial and industrial buildings whose intended uses include the manufacture, preparation, packaging or storage of food. Performance G3.3.2(c) shall not apply to housing. |
G3.3.3An adequate energy supply shall be provided, appropriately located for use by cooking and refrigeration appliances. |
|
G3.3.4Space and facilities shall be provided within each household unit, or grouped elsewhere in a convenient location. |
|
G3.3.5Where facilities are provided for people with disabilities they shall be accessible. |
Performance G3.3.5 shall apply only to camping grounds and accessible accommodation units in communal residential buildings. |
G3.3.6Spaces in buildings shall be protected from the likelihood of contamination or vermin entering areas used for the storage, processing or preparation of food, and shall have a means of preventing contamination spreading from these areas to other spaces. |
Performance G3.3.6 shall apply to commercial or industrial buildings whose intended uses include the handling of perishable food, the medical treatment of humans or animals, the slaughter of animals or the reception of dead bodies. |
Schedule 1 clause G3.1(c) limit on application: amended, on 29 December 2000, by regulation 4(1) of the Building Amendment Regulations 2000 (SR 2000/119).
Schedule 1 second clause G3.2.2 number: revoked, on 22 December 1994, by regulation 9 of the Building Regulations 1992, Amendment No 1 (SR 1994/263).
Schedule 1 G3.2.3 number: inserted, on 22 December 1994, by regulation 9 of the Building Regulations 1992, Amendment No 1 (SR 1994/263).
Clause G4—Ventilation
| Provisions | Limits on application |
|---|---|
Objective |
|
G4.1The objective of this provision is to safeguard people from illness or loss of amenity due to lack of fresh air. |
|
Functional requirement |
|
G4.2Spaces within buildings shall be provided with adequate ventilation consistent with their maximum occupancy and their intended use. |
|
Performance |
|
G4.3.1Spaces within buildings shall have means of ventilation with outdoor air that will provide an adequate number of air changes to maintain air purity. |
|
G4.3.2Mechanical air-handling systems shall be constructed and maintained in a manner that prevents harmful bacteria, pathogens and allergens from multiplying within them. |
|
G4.3.3Buildings shall have a means of collecting or otherwise removing the following products from the spaces in which they are generated: (a)cooking fumes and odours, (b)moisture from laundering, utensil washing, bathing and showering, (c)odours from sanitary and waste storage spaces, (d)gaseous by-products and excessive moisture from commercial or industrial processes, (e)poisonous fumes and gases, (f)flammable fumes and gases, (g)airborne particles, (h)bacteria, viruses or other pathogens, or (i)products of combustion. |
|
G4.3.4Contaminated air shall be disposed of in a way which avoids creating a nuisance or hazard to people and other property. |
|
G4.3.5The quantities of air supplied for ventilation shall meet the additional demands of any fixed combustion appliances. |
Schedule 1 clause G4.2: amended, on 11 September 1997, by regulation 3(1) of the Building Amendment Regulations 1997 (SR 1997/156).
Schedule 1 clause G4.3.3(b): amended, on 11 September 1997, by regulation 3(2) of the Building Amendment Regulations 1997 (SR 1997/156).
Clause G5—Interior environment
| Provisions | Limits on application |
|---|---|
Objective |
|
G5.1The objective of this provision is to: (a)safeguard people from illness caused by low air temperature, (b)safeguard people from injury or loss of amenity caused by inadequate activity space, (c)safeguard people from injury caused by unsafe installations, and (d)ensure that people with disabilities are able to carry out normal activities and processes within buildings. |
Objective G5.1(d) shall apply to those buildings to which section 47A of the Act applies. |
Functional requirement |
|
G5.2.1Buildings shall be constructed to provide: (a)an adequate, controlled interior temperature, (b)adequate activity space for the intended use, and (c)accessible spaces and facilities. |
Requirement G5.2.1(a) shall apply only to habitable spaces, bathrooms and recreation rooms in old people’s homes and early childhood centres. Requirement G5.2.1(b) shall apply only to old people’s homes. Requirement G5.2.1(c) shall apply only to communal residential, communal non-residential, and commercial buildings. |
G5.2.2Heating appliances in buildings shall be installed in a way that reduces the likelihood of injury. |
|
Performance |
|
G5.3.1Habitable spaces, bathrooms and recreation rooms shall have provision for maintaining the internal temperature at no less than 16°C measured at 750 mm above floor level, while the space is adequately ventilated. |
Performance G5.3.1 shall apply only to old people’s homes and early childhood centres. |
G5.3.2Heating appliances, and any attached cables, pipes or other fittings shall be securely fixed in place. |
Performance G5.3.2 shall apply only to old people’s homes and early childhood centres. |
G5.3.3Habitable spaces shall have sufficient space for activity, furniture, and sanitary and mobility aids. |
Performance G5.3.3 shall apply only to old people’s homes. |
G5.3.4Where reception counters or desks are provided for public use, at least one counter or desk shall be accessible. |
Performance G5.3.4 applies only to communal residential, communal non-residential, and commercial buildings. |
G5.3.5Buildings shall be provided with listening systems which enable enhanced hearing by people with hearing aids. |
Performance G5.3.5 applies only to:
|
G5.3.6Enhanced listening systems shall be identified by signs complying with Clause F8 Signs. |
Schedule 1 clause G5.1(d) limit on application: amended, on 29 December 2000, by regulation 4(1) of the Building Amendment Regulations 2000 (SR 2000/119).
Schedule 1 clause G5.2.1(b) limit on application: amended, on 22 December 1994, by regulation 10 of the Building Regulations 1992, Amendment No 1 (SR 1994/263).
Clause G6—Airborne and impact sound
| Provisions | Limits on application |
|---|---|
Objective |
|
G6.1The objective of this provision is to safeguard people from illness or loss of amenity as a result of undue noise being transmitted between abutting occupancies. |
|
Functional requirement |
|
G6.2Building elements which are common between occupancies, shall be constructed to prevent undue noise transmission from other occupancies or common spaces, to the habitable spaces of household units. |
|
Performance |
|
G6.3.1The Sound Transmission Class of walls, floors and ceilings, shall be no less than 55. |
|
G6.3.2The Impact Insulation Class of floors shall be no less than 55. |
Clause G7—Natural light
| Provisions | Limits on application |
|---|---|
Objective |
|
G7.1The objective of this provision is to safeguard people from illness or loss of amenity due to isolation from natural light and the outside environment. |
|
Functional requirement |
|
G7.2Habitable spaces shall provide adequate openings for natural light and for a visual awareness of the outside environment. |
Requirement G7.2 shall apply only to housing, old people’s homes and early childhood centres. |
Performance |
|
G7.3.1Natural light shall provide an illuminance of no less than 30 lux at floor level for 75% of the standard year. |
|
G7.3.2Openings to give awareness of the outside shall be transparent and provided in suitable locations. |
Clause G8—Artificial light
| Provisions | Limits on application |
|---|---|
Objective |
|
G8.1The objective of this provision is to safeguard people from injury due to lack of adequate lighting. |
|
Functional requirement |
|
G8.2Spaces within buildings used by people, shall be provided with adequate artificial lighting which, when activated in the absence of sufficient natural light, will enable safe movement. |
Requirement G8.2 shall apply to:
|
Performance |
|
G8.3Illuminance at floor level shall be no less than 20 lux. |
Performance G8.3 does not apply during a failure of the main lighting, when the requirements in Clause F6 Visibility in escape routes apply. |
Schedule 1 clause G8.2 limit on application (a): amended, on 31 October 2008, by regulation 11(1) of the Building (Building Code: Backcountry Huts) Amendment Regulations 2008 (SR 2008/358).
Schedule 1 clause G8.2 limit on application (b): amended, on 31 October 2008, by regulation 11(2) of the Building (Building Code: Backcountry Huts) Amendment Regulations 2008 (SR 2008/358).
Schedule 1 clause G8.2 limit on application (c): amended, on 31 October 2008, by regulation 11(3) of the Building (Building Code: Backcountry Huts) Amendment Regulations 2008 (SR 2008/358).
Schedule 1 clause G8.3 limit on application: substituted, on 21 June 2007, by regulation 6(5) of the Building Amendment Regulations 2007 (SR 2007/124).
Clause G9—Electricity
| Provisions | Limits on application |
|---|---|
Objective |
|
G9.1The objective of this provision is to ensure that: (a)in buildings supplied with electricity, the electrical installation has safeguards against outbreak of fire and personal injury, and (b)people with disabilities are able to carry out normal activities and processes within buildings. |
Objective G9.1(b) shall apply only to those buildings to which section 47A of the Act applies. |
Functional requirement |
|
G9.2Where provided in a building, electrical installations shall be safe for their intended use. |
|
Performance |
|
G9.3.1The electrical installation shall incorporate systems to: (a)protect people from contact with parts of the installation which are live during normal operation, and to prevent parts of the installation or other building elements becoming live during fault conditions, (b)permit the safe isolation of the installation and of electrical fittings and appliances, (c)safeguard people from excessive temperatures resulting from either normal operation of electrical equipment, or from currents which could exceed the installation rating, (d)safeguard people from injury which may result from electromechanical stress in electrical components caused by currents in excess of the installation rating, (e)protect building elements from risk of ignition, impairment of their physical or mechanical properties, or function, due to temperature increases resulting from heat transfer or electric arc, (f)operate safely in its intended environment, and (g)safeguard against ignition of the surrounding atmosphere where it is potentially flammable or explosive. |
|
G9.3.2An electrical installation supplying an essential service shall: (a)maintain the supply for a time appropriate to that service, and (b)be capable of being isolated from the supply system, independently of the remainder of the installation. |
|
G9.3.3An electrical installation connected to an electrical supply system, shall contain safeguards which protect the safety features of the external supply. |
|
G9.3.4In buildings intended for use by people with disabilities, light switches and plug socket outlets shall be accessible and usable. |
Performance G9.3.4 shall not apply to housing, outbuildings, ancillary buildings, and to industrial buildings where no more than 10 people are employed. |
Schedule 1 clause G9.1(b) limit on application: amended, on 29 December 2000, by regulation 4(1) of the Building Amendment Regulations 2000 (SR 2000/119).
Clause G10—Piped services
| Provisions | Limits on application |
|---|---|
Objective |
|
G10.1The objective of this provision is to safeguard people from injury or illness caused by extreme temperatures or hazardous substances associated with building services. |
|
Functional requirement |
|
G10.2In buildings provided with potentially hazardous services containing hot, cold, flammable, corrosive or toxic fluids, the installations shall be constructed to provide adequate safety for people. |
|
Performance |
|
G10.3.1Piping systems shall be constructed to avoid the likelihood of: (a)significant leakage or damage during normal or reasonably foreseeable abnormal conditions, (b)detrimental contamination of the contents by other substances, (c)adverse interaction between services, or between piping and electrical systems, and (d)people having contact with pipes which could cause them harm. |
|
G10.3.2Provision shall be made for the ready removal of moisture or condensate in gas pipes. |
|
G10.3.3Pipes shall be protected against corrosion in the environment of their use. |
|
G10.3.4Piping systems shall be identified with markings if the contents are not readily apparent from the location or associated equipment. |
|
G10.3.5Enclosed spaces shall be constructed to avoid the likelihood of accumulating vented or leaking gas. |
|
G10.3.6Piped systems shall have isolation devices which permit the installation or individual items of apparatus to be isolated from the supply system, for maintenance, testing, fault detection and repair. |
Clause G11—Gas as an energy source
| Provisions | Limits on application |
|---|---|
Objective |
|
G11.1The objective of this provision is to: (a)safeguard people from injury arising from the use of gas as an energy source, (b)safeguard people and other property from the risk of fire or explosion, and (c)safeguard people from loss of amenity due to the gas supply being inadequate for the intended use. |
|
Functional requirement |
|
G11.2In buildings where gas is used as an energy source, the supply system shall be safe and adequate for its intended use. |
|
Performance |
|
G11.3.1Supply systems shall be constructed to maintain a safe pressure range appropriate to the appliances and the type of gas used. |
|
G11.3.2The gas supply to all appliances in a single ventilated space, shall be fitted with an automatic cut-off activated by failure of any continuous forced ventilation system used for combustion, ventilation or safe operation of a fixed gas appliance. |
|
G11.3.3A flued fixed gas appliance shall have no adverse interaction with any other flued appliance. |
|
G11.3.4Supply systems shall have isolation devices which permit the whole installation, or individual items of apparatus, to be isolated from the supply for maintenance, testing, fault detection or repair. |
|
G11.3.5Where gas is supplied from an external source, the supply system within buildings shall be constructed to avoid the likelihood of: (a)contamination of the external supply from other gas sources within the building, (b)adverse effects on the pressure of the external supply, and (c)the external supply pipe acting as an earthing conductor. |
|
G11.3.6The location and installation of meters and service risers shall meet the requirements of the network utility operator. |
Clause G12—Water supplies
| Provisions | Limits on application |
|---|---|
Objective |
|
G12.1The objective of this provision is to— (a)safeguard people from illness or injury caused by contaminated water: (b)safeguard people from injury caused by hot water system explosion, or from contact with excessively hot water: (c)safeguard people from loss of amenity arising from— (i)a lack of hot water for personal hygiene; or (ii)water for human consumption that is offensive in appearance, odour, or taste: (d)ensure that people with disabilities are able to carry out normal activities and functions within buildings. |
Objective G12.1(d) applies only to those buildings to which section 47A of the Act applies. |
Functional requirement |
|
G12.2Buildings provided with water outlets, sanitary fixtures, or sanitary appliances must have safe and adequate water supplies. |
|
Performance |
|
G12.3.1Water intended for human consumption, food preparation, utensil washing, or oral hygiene must be potable. |
Performance G12.3.1 does not apply to backcountry huts. |
G12.3.2A potable water supply system must be— (a)protected from contamination; and (b)installed in a manner that avoids the likelihood of contamination within the system and the water main; and (c)installed using components that will not contaminate the water. |
|
G12.3.3A non-potable water supply system used for personal hygiene must be installed in a manner that avoids the likelihood of illness or injury being caused by the system. |
|
G12.3.4Water pipes and outlets provided with non-potable water must be clearly identified. |
|
G12.3.5Sanitary fixtures and sanitary appliances must be provided with hot water when intended to be used for— (a)utensil washing; and (b)personal washing, showering, or bathing. |
Performance G12.3.5(b) applies to only housing, retirement homes, and early childhood centres. |
G12.3.6If hot water is provided to sanitary fixtures and sanitary appliances used for personal hygiene, it must be delivered at a temperature that avoids the likelihood of scalding. |
|
G12.3.7Water supply systems must be installed in a manner that— (a)pipes water to sanitary fixtures and sanitary appliances at flow rates that are adequate for the correct functioning of those fixtures and appliances under normal conditions; and (b)avoids the likelihood of leakage; and (c)allows reasonable access to components likely to need maintenance; and (d)allows the system and any backflow prevention devices to be isolated for testing and maintenance. |
|
G12.3.8Vessels used for producing or storing hot water must be provided with safety features that— (a)relieve excessive pressure during both normal and abnormal conditions; and (b)limit temperatures to avoid the likelihood of flash steam production in the event of rupture. |
|
G12.3.9A hot water system must be capable of being controlled to prevent the growth of legionella bacteria. |
|
G12.3.10Water supply taps must be accessible and usable for people with disabilities. |
Performance G12.3.10 applies only to those buildings to which section 47A of the Act applies. |
Schedule 1 clause G12: substituted, on 3 January 2002, by regulation 3(10) of the Building Amendment Regulations 2001 (SR 2001/374).
Schedule 1 clause G12.3.1 limit on application: inserted, on 31 October 2008, by regulation 12 of the Building (Building Code: Backcountry Huts) Amendment Regulations 2008 (SR 2008/358).
Clause G13—Foul water
| Provisions | Limits on application |
|---|---|
Objective |
|
G13.1The objective of this provision is to: (a)safeguard people from illness due to infection or contamination resulting from personal hygiene activities, and (b)safeguard people from loss of amenity due to the presence of unpleasant odours or the accumulation of offensive matter resulting from foul water disposal. |
|
Functional requirement |
|
G13.2Buildings in which sanitary fixtures and sanitary appliances using water-borne waste disposal are installed must be provided with— (a)an adequate plumbing and drainage system to carry foul water to appropriate outfalls; and (b)if no sewer is available, an adequate system for the storage, treatment, and disposal of foul water. |
|
Performance |
|
G13.3.1The plumbing system shall be constructed to: (a)convey foul water from buildings to a drainage system, (b)avoid the likelihood of blockage and leakage, (c)avoid the likelihood of foul air and gases entering buildings, and (d)provide reasonable access for maintenance and clearing blockages. |
|
G13.3.2The drainage system shall: (a)convey foul water to an appropriate outfall, (b)be constructed to avoid the likelihood of blockage, (c)be supported, jointed and protected in a way that will avoid the likelihood of penetration of roots or the entry of ground water, (d)be provided with reasonable access for maintenance and clearing blockages, (e)be ventilated to avoid the likelihood of foul air and gases accumulating in the drainage system and sewer, and (f)be constructed to avoid the likelihood of damage from superimposed loads or normal ground movement. |
|
G13.3.3Where a sewer connection is available, the drainage system shall be connected to the sewer, and the connection shall be made in a manner that avoids damage to the sewer and is to the approval of the network utility operator. |
|
G13.3.4If no sewer is available, facilities for the storage, treatment, and disposal of foul water must be constructed— (a)with adequate capacity for the volume of foul water and the frequency of disposal; and (b)with adequate vehicle access for collection if required; and (c)to avoid the likelihood of contamination of any potable water supplies in compliance with Clause G12 Water supplies; and (d)to avoid the likelihood of contamination of soils, ground water, and waterways except as permitted under the Resource Management Act 1991; and (e)from materials that are impervious both to the foul water for which disposal is required, and to water; and (f)to avoid the likelihood of blockage and leakage; and (g)to avoid the likelihood of foul air and gases accumulating within or entering into buildings; and (h)to avoid the likelihood of unauthorised access by people; and (i)to permit easy cleaning and maintenance; and (j)to avoid the likelihood of damage from superimposed loads or normal ground movement; and (k)if those facilities are buried underground, to resist hydrostatic uplift pressures. |
Schedule 1 clause G13.2: substituted, on 21 June 2007, by regulation 7(1) of the Building Amendment Regulations 2007 (SR 2007/124).
Schedule 1 clause G13.3.4: substituted, on 21 June 2007, by regulation 7(2) of the Building Amendment Regulations 2007 (SR 2007/124).
Clause G14—Industrial liquid waste
| Provisions | Limits on application |
|---|---|
Objective |
|
G14.1The objective of this provision is to safeguard people from injury or illness caused by infection or contamination resulting from industrial liquid waste. |
|
Functional requirement |
|
G14.2Buildings, in which industrial liquid waste is generated shall be provided with adequate spaces and facilities for the safe and hygienic collection, holding, treatment and disposal of the waste. |
|
Performance |
|
G14.3.1Industrial liquid waste shall be conveyed to storage containers and within disposal systems in a way which will: (a)transfer wastes from buildings safely and hygienically, (b)avoid the likelihood of blockage and leakage, (c)avoid the likelihood of foul air and gases entering buildings, and (d)provide reasonable access for clearing of blockages. |
|
G14.3.2Facilities for the storage, treatment, and disposal of industrial liquid waste must be constructed— (a)with adequate capacity for the volume of waste and the frequency of disposal; and (b)with adequate vehicle access for collection if required; and (c)to avoid the likelihood of contamination of any potable water supplies in compliance with Clause G12 Water supplies; and (d)to avoid the likelihood of contamination of soils, ground water, and waterways except as permitted under the Resource Management Act 1991; and (e)from materials that are impervious both to the waste for which disposal is required, and to water; and (f)to avoid the likelihood of blockage and leakage; and (g)to avoid the likelihood of foul air and gases accumulating within or entering into buildings; and (h)to avoid the likelihood of unauthorised access by people; and (i)to permit easy cleaning and maintenance; and (j)to avoid the likelihood of damage from superimposed loads or normal ground movement; and (k)if those facilities are buried underground, to resist hydrostatic uplift pressures. |
Schedule 1 clause G14.3.2: substituted, on 21 June 2007, by regulation 8 of the Building Amendment Regulations 2007 (SR 2007/124).
Clause G15—Solid waste
| Provisions | Limits on application |
|---|---|
Objective |
|
G15.1The objective of this provision is to safeguard people from injury or illness caused by infection or contamination from solid waste. |
|
Functional requirement |
|
G15.2Buildings shall be provided with space and facilities for the collection, and safe hygienic holding prior to disposal, of solid waste arising from the intended use of the buildings. |
Requirement G15.2 shall not apply to detached dwellings, household units of multi-unit dwellings, outbuildings or ancilliary buildings if there is independent access or private open space at ground level. |
Performance |
|
G15.3.1Where provision is made within buildings for the collection and temporary holding of solid waste, the spaces provided shall be: (a)of sufficient size for the volume of waste and frequency of disposal, (b)provided with reasonable access for the depositing and collection of the waste, (c)capable of maintaining sanitary conditions having regard to the types of waste and storage containers, and (d)capable of maintaining the appropriate temperature for the type of waste stored. |
|
G15.3.2Where a rubbish chute is provided, it shall be located and constructed to: (a)convey the solid waste to an appropriate storage container, (b)avoid the likelihood of blockage or leakage, (c)permit easy cleaning and maintenance, (d)avoid the likelihood of foul air or gases accumulating or entering the building, (e)avoid the likelihood of the spread of fire beyond the refuse chute, (f)have openings that allow waste to be safely deposited in the chute, and (g)restrict access by children, animals and vermin. |
|
G15.3.3Where it is acceptable to the network utility operator, solid waste which has been suitably treated for disposal to a sewer may be discharged via a foul water drain complying with Clause G13 Foul Water. |
Schedule 1 clause G15.3.2(f): amended, on 22 December 1994, by regulation 13 of the Building Regulations 1992, Amendment No 1 (SR 1994/263).
Clause H1—Energy efficiency provisions
| Provisions | Limits on application |
|---|---|
Objective |
|
H1.1The objective of this provision is to facilitate efficient use of energy. |
Objective H1.1 applies only when the energy is sourced from a network utility operator or a depletable energy resource. |
Functional requirement |
|
H1.2Buildings must be constructed to achieve an adequate degree of energy efficiency when that energy is used for— (a)modifying temperature, modifying humidity, providing ventilation, or doing all or any of those things; or (b)providing hot water to and from sanitary fixtures or sanitary appliances, or both; or (c)providing artificial lighting. |
Requirement H1.2(a) does not apply to assembly service buildings, industrial buildings, outbuildings, or ancillary buildings. Requirement H1.2(c) applies only to commercial buildings and communal non-residential buildings whose floor area is greater than 300 m2. |
Performance |
|
H1.3.1The building envelope enclosing spaces where the temperature or humidity (or both) are modified must be constructed to— (a)provide adequate thermal resistance; and (b)limit uncontrollable airflow. |
|
H1.3.2[Revoked] |
|
H1.3.2A[Revoked] |
|
H1.3.2B[Revoked] |
|
H1.3.2C[Revoked] |
|
H1.3.2D[Revoked] |
|
H1.3.2EBuildings must be constructed to ensure that their building performance index does not exceed 1.55. |
Performance H1.3.2E applies only to housing. |
H1.3.3Account must be taken of physical conditions likely to affect energy performance of buildings, including— (a)the thermal mass of building elements; and (b)the building orientation and shape; and (c)the airtightness of the building envelope; and (d)the heat gains from services, processes and occupants; and (e)the local climate; and (f)heat gains from solar radiation. |
|
H1.3.4Systems for the heating, storage, or distribution of hot water to and from sanitary fixtures or sanitary appliances must, having regard to the energy source used,— (a)limit the energy lost in the heating process; and (b)be constructed to limit heat losses from storage vessels and from distribution systems; and (c)be constructed to facilitate the efficient use of hot water. |
Performance H1.3.4(b) does not apply to individual storage vessels that are greater than 700 litres in capacity. Performance H1.3.4(c) applies only to housing. |
H1.3.5Artificial lighting fixtures must— (a)be located and sized to limit energy use, consistent with the intended use of space; and (b)be fitted with a means to enable light intensities to be reduced, consistent with reduced activity in the space. |
Performance H1.3.5 does not apply to lighting provided solely to meet the requirements of Clause F6. |
H1.3.6HVAC systems must be located, constructed, and installed to– – (a)limit energy use, consistent with the intended use of space; and (b)enable them to be maintained to ensure their use of energy remains limited, consistent with the intended use of space. |
Performance H1.3.6 applies only to commercial buildings. |
Schedule 1: continued in force, on 31 March 2005, by regulation 8(2)(a) of the Building (Forms) Regulations 2004 (SR 2004/385).
Schedule 1 clause H1: substituted, on 29 December 2000, by regulation 5 of the Building Amendment Regulations 2000 (SR 2000/119).
Schedule 1 clause H1.2(a): substituted, on 1 February 2009, by regulation 5 of the Building (Building Code: Energy Efficiency of Temperature, Humidity, and Ventilation Systems) Amendment Regulations 2008 (SR 2008/97).
Schedule 1 clause H1.2(b): amended, on 1 February 2009, by regulation 4 of the Building (Building Code: Energy Efficiency of Domestic Hot Water Systems) Amendment Regulations 2008 (SR 2008/256).
Schedule 1 clause H1.3.2: revoked, on 31 October 2007, by regulation 5 of the Building Amendment Regulations (No 2) 2007 (SR 2007/226).
Schedule 1 clause H1.3.2A: revoked, on 30 June 2008, by regulation 6 of the Building Amendment Regulations (No 2) 2007 (SR 2007/226).
Schedule 1 clause H1.3.2B: revoked, on 30 June 2008, by regulation 6 of the Building Amendment Regulations (No 2) 2007 (SR 2007/226).
Schedule 1 clause H1.3.2C: revoked, on 30 September 2008, by regulation 7(1) of the Building Amendment Regulations (No 2) 2007 (SR 2007/226).
Schedule 1 clause H1.3.2D: revoked, on 30 September 2008, by regulation 7(1) of the Building Amendment Regulations (No 2) 2007 (SR 2007/226).
Schedule 1 clause H1.3.2E: inserted, on 30 September 2008, by regulation 7(1) of the Building Amendment Regulations (No 2) 2007 (SR 2007/226).
Schedule 1 clause H1.3.4: substituted, on 1 February 2009, by regulation 5 of the Building (Building Code: Energy Efficiency of Domestic Hot Water Systems) Amendment Regulations 2008 (SR 2008/256).
Schedule 1 clause H1.3.6: added, on 1 February 2009, by regulation 6 of the Building (Building Code: Energy Efficiency of Temperature, Humidity, and Ventilation Systems) Amendment Regulations 2008 (SR 2008/97).
Schedule 2
Schedule 2: revoked for all purposes, on 31 May 2006, by regulation 8(2)(b) of the Building (Forms) Regulations 2004 (SR 2004/385).
Marie Shroff,
Clerk of the Executive Council.
Issued under the authority of the Acts and Regulations Publication Act 1989.
Date of notification in Gazette: 11 June 1992.
Building (Forms) Regulations 2004
(SR 2004/385)
Silvia Cartwright, Governor-General
Order in Council
At Wellington this 8th day of November 2004
Present:
Her Excellency the Governor-General in Council
Pursuant to section 402 of the Building Act 2004, Her Excellency the Governor-General, acting on the advice and with the consent of the Executive Council and on the recommendation of the Minister for Building Issues, makes the following regulations.
Regulations
1 Title
These regulations are the Building (Forms) Regulations 2004.
2 Commencement
(1)
These regulations (except regulations 5 and 8 and Part 2 of the Schedule) come into force on 30 November 2004.
(2)
Regulations 5 and 8 and Part 2 of the Schedule come into force on 31 March 2005.
Revocation
8 Revocation
(1)
The Building Regulations 1992 (SR 1992/150) are revoked.
(2)
However, despite the revocation of the Building Regulations 1992,—
(a)
regulation 3 and Schedule 1 of those regulations continue in force: and
(b)
so much of regulation 4 and Schedule 2 of those regulations as relate to forms 16 (application for approval as an individual building certifier) and 17 (application for approval as a corporate building certifier) continue in force and apply for the purposes of section 441 of the Act until 31 May 2006.
Diane Morcom,
Clerk of the Executive Council.
Date of notification in Gazette: 11 November 2004.
Building Amendment Regulations (No 2) 2007
(SR 2007/226)
Dame Sian Elias, Administrator of the Government
Order in Council
At Wellington this 13th day of August 2007
Present:
The Right Hon Helen Clark presiding in Council
Pursuant to section 400 of the Building Act 2004, Her Excellency the Administrator of the Government, acting on the advice and with the consent of the Executive Council, and on the recommendation of the Minister (as defined by section 7 of that Act) made, as required by section 403(2) of that Act, after he or she became satisfied that the chief executive (as so defined) has consulted in accordance with section 403(3) and (4) of that Act, makes the following regulations.
Regulations
1 Title
These regulations are the Building Amendment Regulations (No 2) 2007.
2 Commencement
(1)
These regulations (other than regulations 6 and 7) come into force on 31 October 2007.
(2)
Regulation 6 comes into force on 30 June 2008.
(3)
Regulation 7 comes into force on 30 September 2008.
8 Saving: building work not affected by amendments
(1)
The building code set out in Schedule 1 of the principal regulations applies to the following building work as if these regulations had not been made:
(a)
building work that is in climate zone 1, climate zone 2, or climate zone 3, is building work for which a building consent is required, and is covered by an application—
(i)
for a building consent or a certificate of acceptance; and
(ii)
made before the close of 30 October 2007:
(b)
building work that is in climate zone 1 or climate zone 2, is building work for which a building consent is required, and is covered by an application—
(i)
for a building consent or a certificate of acceptance; and
(ii)
made after the close of 30 October 2007 and before the close of 29 June 2008:
(c)
building work that is in climate zone 1, is building work for which a building consent is required, and is covered by an application—
(i)
for a building consent or a certificate of acceptance; and
(ii)
made after the close of 29 June 2008 and before the close of 29 September 2008.
(2)
For the purpose of subclause (1)(b), building work partly in climate zone 3 and partly in climate zone 2 must be treated as if it were building work in climate zone 2.
(3)
For the purpose of subclause (1)(c), building work partly in climate zone 2 and partly in climate zone 1 must be treated as if it were building work in climate zone 1.
Diane Morcom,
Clerk of the Executive Council.
Date of notification in Gazette: 16 August 2007.
Building (Building Code: Energy Efficiency of Temperature, Humidity, and Ventilation Systems) Amendment Regulations 2008
(SR 2008/97)
Anand Satyanand, Governor-General
Order in Council
At Wellington this 7th day of April 2008
Present:
His Excellency the Governor-General in Council
Pursuant to section 400 of the Building Act 2004, His Excellency the Governor-General, acting on the advice and with the consent of the Executive Council, and on the recommendation of the Minister (as defined by section 7 of that Act) made, as required by section 403(2) of that Act, after he or she became satisfied that the chief executive (as so defined) has consulted in accordance with section 403(3) and (4) of that Act, makes the following regulations.
Regulations
1 Title
2 Commencement
These regulations come into force on 1 February 2009.
7 Saving: building work not affected by amendments
The building code set out in Schedule 1 of the principal regulations applies as if these regulations had not been made to building work covered by an application—
(a)
for a building consent or a certificate of acceptance; and
(b)
made before the close of 31 January 2009.
Diane Morcom,
Clerk of the Executive Council.
Date of notification in Gazette: 10 April 2008.
Building (Building Code: Energy Efficiency of Domestic Hot Water Systems) Amendment Regulations 2008
(SR 2008/256)
Rt Hon Dame Sian Elias, Administrator of the Government
Order in Council
At Wellington this 11th day of August 2008
Present:
Her Excellency the Administrator of the Government in Council
Pursuant to section 400 of the Building Act 2004, Her Excellency the Administrator of the Government, acting on the advice and with the consent of the Executive Council, and on the recommendation of the Minister (as defined by section 7 of that Act) made, as required by section 403(2) of that Act, after he or she became satisfied that the chief executive (as so defined) has consulted in accordance with section 403(3) and (4) of that Act, makes the following regulations.
Regulations
1 Title
These regulations are the Building (Building Code: Energy Efficiency of Domestic Hot Water Systems) Amendment Regulations 2008.
2 Commencement
These regulations come into force on 1 February 2009.
6 Saving: building work not affected by amendments
The building code set out in Schedule 1 of the principal regulations applies as if these regulations had not been made, to building work covered by an application that is—
(a)
for a building consent or certificate of acceptance; and
(b)
made before the close of 31 January 2009.
Rebecca Kitteridge,
Clerk of the Executive Council.
Date of notification in Gazette: 14 August 2008.
Contents
-
1
General
-
2
Status of reprints
-
3
How reprints are prepared
-
4
Changes made under section 17C of the Acts and Regulations Publication Act 1989
-
5
List of amendments incorporated in this reprint (most recent first)
Notes
1 General
This is a reprint of the Building Regulations 1992. The reprint incorporates all the amendments to the regulations as at 1 February 2009, as specified in the list of amendments at the end of these notes.
Relevant provisions of any amending enactments that have yet to come into force or that contain relevant transitional or savings provisions are also included, after the principal enactment, in chronological order.
2 Status of reprints
Under section 16D of the Acts and Regulations Publication Act 1989, reprints are presumed to correctly state, as at the date of the reprint, the law enacted by the principal enactment and by the amendments to that enactment. This presumption applies even though editorial changes authorised by section 17C of the Acts and Regulations Publication Act 1989 have been made in the reprint.
This presumption may be rebutted by producing the official volumes of statutes or statutory regulations in which the principal enactment and its amendments are contained.
3 How reprints are prepared
A number of editorial conventions are followed in the preparation of reprints. For example, the enacting words are not included in Acts, and provisions that are repealed or revoked are omitted. For a detailed list of the editorial conventions, see http://www.pco.parliament.govt.nz/legislation/reprints.shtml or Part 8 of the Tables of Acts and Ordinances and Statutory Regulations, and Deemed Regulations in Force.
4 Changes made under section 17C of the Acts and Regulations Publication Act 1989
Section 17C of the Acts and Regulations Publication Act 1989 authorises the making of editorial changes in a reprint as set out in sections 17D and 17E of that Act so that, to the extent permitted, the format and style of the reprinted enactment is consistent with current legislative drafting practice. Changes that would alter the effect of the legislation are not permitted.
A new format of legislation was introduced on 1 January 2000. Changes to legislative drafting style have also been made since 1997, and are ongoing. To the extent permitted by section 17C of the Acts and Regulations Publication Act 1989, all legislation reprinted after 1 January 2000 is in the new format for legislation and reflects current drafting practice at the time of the reprint.
In outline, the editorial changes made in reprints under the authority of section 17C of the Acts and Regulations Publication Act 1989 are set out below, and they have been applied, where relevant, in the preparation of this reprint:
-
•
omission of unnecessary referential words (such as
“of this section”
and“of this Act”
) -
•
typeface and type size (Times Roman, generally in 11.5 point)
-
•
layout of provisions, including:
-
•
indentation
-
•
position of section headings (eg, the number and heading now appear above the section)
-
•
-
•
format of definitions (eg, the defined term now appears in bold type, without quotation marks)
-
•
format of dates (eg, a date formerly expressed as
“the 1st day of January 1999”
is now expressed as“1 January 1999”
) -
•
position of the date of assent (it now appears on the front page of each Act)
-
•
punctuation (eg, colons are not used after definitions)
-
•
Parts numbered with roman numerals are replaced with arabic numerals, and all cross-references are changed accordingly
-
•
case and appearance of letters and words, including:
-
•
format of headings (eg, headings where each word formerly appeared with an initial capital letter followed by small capital letters are amended so that the heading appears in bold, with only the first word (and any proper nouns) appearing with an initial capital letter)
-
•
small capital letters in section and subsection references are now capital letters
-
•
-
•
schedules are renumbered (eg, Schedule 1 replaces First Schedule), and all cross-references are changed accordingly
-
•
running heads (the information that appears at the top of each page)
-
•
format of two-column schedules of consequential amendments, and schedules of repeals (eg, they are rearranged into alphabetical order, rather than chronological).
5 List of amendments incorporated in this reprint (most recent first)
Building (Building Code: Backcountry Huts) Amendment Regulations 2008 (SR 2008/358)
Building (Building Code: Energy Efficiency of Domestic Hot Water Systems) Amendment Regulations 2008 (SR 2008/256)
Building Amendment Regulations (No 2) 2007 (SR 2007/226)
Building Amendment Regulations 2007 (SR 2007/124)
Education Amendment Act 2006 (2006 No 19): section 60(2)
Building (Forms) Regulations 2004 (SR 2004/385): regulation 8
Building Amendment Regulations 2004 (SR 2004/317)
Building Amendment Regulations 2003 (SR 2003/61)
Building Amendment Regulations 2001 (SR 2001/374)
Building Amendment Regulations 2000 (SR 2000/119)
Building Amendment Regulations 1997 (SR 1997/156)
Hazardous Substances and New Organisms Act 1996 (1996 No 30): section 150(1)
Building Regulations 1992, Amendment No 1 (SR 1994/263)
"Related Legislation
"Related Legislation
"Related Legislation
Versions
Building Regulations 1992
RSS feed link copied, you can now paste this link into your feed reader.